引用本文:李 峰,徐丙垠.电力电缆故障冲闪测试放电回路建模[J].电力自动化设备,2011,31(3):
LI Feng,XU Bingyin.Modeling of surge discharge circuit for power cable fault locator[J].Electric Power Automation Equipment,2011,31(3):
【打印本页】   【HTML】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 5613次   下载 2319  
电力电缆故障冲闪测试放电回路建模
李 峰1, 徐丙垠2
1.合肥工业大学 仪器科学与光电工程学院,安徽 合肥 230009;2.山东科汇电力自动化有限公司,山东 淄博 255087
摘要:
对电力电缆故障冲击高压闪络测试(简称冲闪测试)系统的放电响应进行了研究。在只考虑暂态低频分量信号的条件下,利用电缆的均匀传输线T型等效网络,建立了冲闪测试放电回路的集中参数电路模型。根据电缆的结构和材料参数,以及电缆集中参数与其分布参数之间的关系,推导了模型的电流、电压响应近似表达式,以及电流响应的衰减系数和振荡频率表达式。论证了冲闪测试放电回路串联电阻为零时电流、电压响应近似为二阶衰减振荡过程,二次脉冲法冲闪测试放电回路串联电阻不为零时电流响应是过阻尼的负指数衰减过程。模型计算与实验结果的一致性验证了建模的正确性。
关键词:  电力电缆  故障测距  冲闪测试  放电回路  二次脉冲法
DOI:
分类号:
基金项目:
Modeling of surge discharge circuit for power cable fault locator
LI Feng1, XU Bingyin2
1.School of Instrument Science and Photoelectric Engineering,Hefei University of Technology, Hefei 230009,China;2.Shandong Kehui Power Automation Co.,Ltd.,Zibo 255087,China
Abstract:
The current and voltage response of surge discharge circuit to impulse flashover voltage test system is analyzed. When only low frequency transient components are considered,the lumped parameter model of the surge discharge circuit of power cable fault locator is constructed based on the T-type equivalent network of uniform transmission line. According to the geometry and material specifications of power cable,as well as the relationship between its lumped and distributed parameters,the approximate expressions of current and voltage response,as well as the expressions of current attenuation coefficients and oscillation frequency of current response,are deduced. When the series resistance in surge discharge circuit is zero,the current and voltage response are approximately the second-order decaying vibration process. When the series resistance is not zero,the current response to the secondary impulse method is the over-damped negative-exponent decaying process. The results of model calculation are consistent with the experimental results,verifying the correctness of the modeling.
Key words:  power cable  fault locating  impulse flashover voltage test  discharge circuit  secondary impulse method

用微信扫一扫

用微信扫一扫