引用本文:丛 伟,张琳琳,程学启,邱升孝,荀堂生,宋志明.基于故障电流幅值与相位差的电流差动保护判据[J].电力自动化设备,2013,33(5):
CONG Wei,ZHANG Linlin,CHENG Xueqi,QIU Shengxiao,XUN Tangsheng,SONG Zhiming.Criterion of current differential protection based on amplitude and phase difference of fault current[J].Electric Power Automation Equipment,2013,33(5):
【打印本页】   【HTML】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 4641次   下载 1802  
基于故障电流幅值与相位差的电流差动保护判据
丛 伟1, 张琳琳2, 程学启3, 邱升孝3, 荀堂生4, 宋志明4
1.山东大学 电网智能化调度与控制教育部重点实验室,山东 济南 250061;2.山东泰安供电公司,山东 泰安 271000;3.山东潍坊供电公司,山东 潍坊 261021;4.国网技术学院,山东 济南 250002
摘要:
提出了一种基于故障分量电流幅值与相位差的电流差动保护判据,其中差动电流为本侧电流故障分量幅值加上对侧电流故障分量幅值与二者相位差余弦值之积,制动电流为本侧电流故障分量幅值减去对侧电流故障分量幅值与二者相位差余弦值之积。分析了不同系统阻抗、过渡电阻、分布电容对该差动保护判据性能的影响,并与目前广泛应用的故障分量电流相量差动保护判据和标积制动原理的差动保护判据进行了性能上的对比分析,同时采用EMTDC软件进行了算例仿真。分析计算结果表明,所提的差动保护判据在区内故障时的灵敏度更高,区外故障时的安全性更好,在不同系统阻抗、过渡电阻、分布电容条件下均具有良好的性能。
关键词:  故障电流  灵敏度分析  继电保护  幅值  相位差  仿真
DOI:
分类号:
基金项目:国家自然科学基金资助项目(50807032)
Criterion of current differential protection based on amplitude and phase difference of fault current
CONG Wei1, ZHANG Linlin2, CHENG Xueqi3, QIU Shengxiao3, XUN Tangsheng4, SONG Zhiming4
1.Key Laboratory of Power System Intelligent Dispatch and Control,Ministry of Education,Shandong University,Ji’nan 250061,China;2.Shandong Taian Power Supply Company,Taian 271000,China;3.Shandong Weifang Power Supply Company,Weifang 261021,China;4.State Grid of China Technology College,Ji’nan 250002,China
Abstract:
A criterion of current differential protection is proposed,which is based on the amplitude and phase difference of fault current component. The differential current is the sum of the fault current amplitude on own side and the product of that on opposite side and the cosine of phase difference between them,while the braking current is the difference. The influences of system impedance,transition resistance and distributed capacitance on the performance of the proposed criterion are analyzed. It is compared in performance with the fault current phasor differential criterion and the scalar product braking differential criterion. Results of simulation with EMTDC show that,the proposed criterion has higher sensitivity to in-zone faults,higher security for out-zone faults and better performance under different system impedances,transition resistances and distributed capacitances.
Key words:  electric fault currents  sensitivity analysis  relay protection  amplitude  phase difference  computer simulation

用微信扫一扫

用微信扫一扫