基于保护动作信号的配电网区域保护方案
马静1, 张涌新1, 项晓强1, 宋晓辉2, 赵煜1
1.华北电力大学新能源电力系统国家重点实验室,北京102206;2.中国电力科学研究院,北京100192
摘要:
针对多分布式电源和多分支引起本地保护不正确动作的情况,提出一种基于逻辑量信息的配电网区域保护方案。首先分析多分布式电源和多分支线路下本地保护存在的问题,在此基础上,根据断路器配置情况划分保护区域。然后融合现有阶段式过流保护Ⅰ段、Ⅱ段和Ⅲ段启动信息构成区域保护动作判据。IEEE 33节点配电系统算例验证了所提方案能够准确定位区内故障、闭锁区外故障,加速保护动作、缩短故障停电时间。判据以多信息构成冗余,具有较强的容错能力,信息传输量少,对同步性要求低。
关键词:  分布式电源  配电网  区域保护  保护动作信号  继电保护
DOI:10.16081/j.issn.1006-6047.2018.03.005
分类号:TM77
基金项目:国家电网公司总部科技项目(随机负荷与间歇性分布式电源下的主动配电网保护关键技术研究)
Regional protection scheme of distribution network based on operating signal of protection
MA Jing1, ZHANG Yongxin1, XIANG Xiaoqiang1, SONG Xiaohui2, ZHAO Yu1
1.State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University, Beijing 102206, China;2.China Electric Power Research Institute, Beijing 100192, China
Abstract:
Since the local protection may improperly operate due to the multiple DGs(Distributed Generators) and branches, a regional protection scheme of distribution network based on the logical information is proposed. Firstly, the problems of local protection caused by multiple DGs and branches are analyzed, base on which, the protection areas are divided based on breaker configuration. Secondly, the operation criterion of regional protection is constituted by the combination of the start-up information of the section Ⅰ,Ⅱ and Ⅲ of the existing over-current protection. The case study of IEEE 33-bus distribution system shows that the proposed scheme can accurately locate the internal fault, block the protection during the external fault, accelerate the protection operation and shorten the power outage time. The proposed criterion is constituted by redundant information, it has strong fault-tolerant ability, and requires less transinformation and lower information synchronization.
Key words:  distributed power generation  distribution network  regional protection  protection operation signal  relay protection