引用本文:杨晓梅,郭朝云,樊博,罗月婉,肖先勇.采用奇异值梯度信息的暂态电能质量扰动自适应检测方法[J].电力自动化设备,2019,39(6):
YANG Xiaomei,GUO Chaoyun,FAN Bo,LUO Yuewan,XIAO Xianyong.Adaptive detection method of transient power quality disturbance based on singular value gradient information[J].Electric Power Automation Equipment,2019,39(6):
【打印本页】   【HTML】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 4211次   下载 1883  
采用奇异值梯度信息的暂态电能质量扰动自适应检测方法
杨晓梅1, 郭朝云1, 樊博2, 罗月婉1, 肖先勇1
1.四川大学 电气信息学院,四川 成都 610065;2.国网宁夏电力有限公司电力科学研究院,宁夏 银川 750011
摘要:
为了满足对电网非平稳扰动信号快速、准确分析的要求,提出了一种采用奇异值梯度信息的暂态电能质量扰动检测新方法。通过滑动窗奇异值分解(SVD)方法提取信号的变化特征、降低噪声干扰,并通过奇异值梯度求取扰动指示信号,得到初步定位结果。提出无参自适应阈值,进一步抑制噪声干扰并实现对暂态扰动信号的检测定位。所提算法原理简单,无需进行前置滤波及参数调节。一系列仿真试验的对比分析结果表明,所提算法定位准确、抗干扰能力强,对过零点扰动也有较好的检测效果。通过对变电站实际暂态扰动数据的检测分析,进一步验证了所提算法的有效性。
关键词:  暂态电能质量  扰动检测  奇异值分解  奇异值梯度  自适应阈值  抗噪性
DOI:10.16081/j.issn.1006-6047.2019.06.020
分类号:TM761
基金项目:
Adaptive detection method of transient power quality disturbance based on singular value gradient information
YANG Xiaomei1, GUO Chaoyun1, FAN Bo2, LUO Yuewan1, XIAO Xianyong1
1.College of Electrical Engineering and Information Technology, Sichuan University, Chengdu 610065, China;2.Electric Power Research Institute of State Grid Ningxia Electric Power Co.,Ltd.,Yinchuan 750011, China
Abstract:
In order to satisfy the requirement of fast and accurate analysis of non-stationary disturbance signals in power grid, a novel detection method of transient power quality disturbance based on singular value gradient information is proposed. The sliding window SVD(Singular Value Decomposition) method is used to extract the change characteristics of signals and reduce the noise interference. Then the disturbance indication signal is obtained by using the singular value gradient information, and the initial location result is obtained. A parameter-free adaptive threshold is proposed to further suppress the noise interference and detect and locate the transient disturbance signals. The proposed algorithm is simple in principle and does not require pre-filtering and parameter adjustment. The analysis and comparison results of a series of simulation tests show that the proposed algorithm has the advantages of accurate location, strong anti-interference ability and good detection effect on zero-crossing disturbance. The validity of the proposed algorithm is further verified through the detection analysis of the actual transient disturbance data of substation.
Key words:  transient power quality  disturbance detection  singular value decomposition  singular value gradient  adaptive threshold  anti-noise

用微信扫一扫

用微信扫一扫