引用本文:梁浩,谢欢,吴涛,张广韬,訾鹏,张饶,苏为民.某真实连锁故障下自动电压调节器的调节特性仿真分析与评估[J].电力自动化设备,2021,41(6):
LIANG Hao,XIE Huan,WU Tao,ZHANG Guangtao,ZI Peng,ZHANG Rao,SU Weimin.Simulation analysis and performance evaluation of AVR characteristics in real cascading failure[J].Electric Power Automation Equipment,2021,41(6):
【打印本页】   【HTML】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 11029次   下载 1396  
某真实连锁故障下自动电压调节器的调节特性仿真分析与评估
梁浩1, 谢欢1, 吴涛1, 张广韬1, 訾鹏2, 张饶3, 苏为民1
1.国网冀北电力有限公司电力科学研究院,北京 100045;2.国家电网公司华北分部,北京 100010;3.三峡大学 电气工程及其自动化系,湖北 宜昌 443000
摘要:
励磁控制系统在连锁故障下改善系统大干扰后的暂态过程、防止电压失稳等方面意义重大。首先介绍了自动电压调节器(AVR)中定子电流限制环节的相关原理与仿真模型;然后分析了一起现场真实连锁故障对周边某机组的影响及其AVR的响应过程,包括多次强励、定子电流限制动作、机端电压过低引起失稳等;最后利用RTDS软件搭建了单机无穷大一次仿真系统及AVR的主、辅控制环节,通过外部故障模拟与AVR调节特性仿真,重点分析了AVR定子电流限制环节及严重故障下发电机自并励励磁方式的特性并提出优化建议。
关键词:  连锁故障  自动电压调节器  实时数字仿真  电压稳定  定子电流限制
DOI:10.16081/j.epae.202102013
分类号:TM761
基金项目:国家电网公司华北分部科技项目(特高压交直流联合外送的弱送源协调机理研究项目)(520101180050)
Simulation analysis and performance evaluation of AVR characteristics in real cascading failure
LIANG Hao1, XIE Huan1, WU Tao1, ZHANG Guangtao1, ZI Peng2, ZHANG Rao3, SU Weimin1
1.State Grid Jibei Electric Power Co.,Ltd. Research Institute, Beijing 100045, China;2.North China Branch of State Grid Corporation of China, Beijing 100010, China;3.Department of Electrical Engineering and Automation, China Three Gorges University, Yichang 443000, China
Abstract:
It is of great significance for excitation control system to improve the transient process and prevent voltage instability under the condition of cascading failure. The principle and simulation model of SCL(Stator Current Limit) loop of AVR(Automatic Voltage Regulator) are introduced, and the influence of a real field cascading failure on an adjacent generator unit and the response process of its AVR are analyzed, including multiple force excitation, SCL action, instability caused by low terminal voltage, etc. On this basis, the RTDS(Real Time Digital Simulator) is used to build the one-machine infinite-bus primary system and the main and auxiliary control loops of AVR. Through the simulation of external faults and AVR regulating characteristics, the SCL loop of AVR and the characteristics of self-shunt excitation mode of generator under serious faults are analyzed emphatically and the optimization suggestion is proposed.
Key words:  cascading failure  automatic voltage regulator  RTDS  voltage stability  stator current limit