引用本文:王卓雅,郝亮亮,王乐,和敬涵,陈争光.MMC-HVDC系统直流侧非金属性短路故障电流计算方法[J].电力自动化设备,2024,44(3):187-194
WANG Zhuoya,HAO Liangliang,WANG Le,HE Jinghan,CHEN Zhengguang.Calculation method of nonmetallic short circuit fault current in DC side of MMC-HVDC system[J].Electric Power Automation Equipment,2024,44(3):187-194
【打印本页】   【HTML】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 2813次   下载 634 本文二维码信息
码上扫一扫!
MMC-HVDC系统直流侧非金属性短路故障电流计算方法
王卓雅1, 郝亮亮1, 王乐1, 和敬涵1, 陈争光2
1.北京交通大学 电气工程学院,北京 100044;2.国家电网有限公司,北京 100031
摘要:
为研究基于模块化多电平换流器的高压直流输电(MMC-HVDC)系统直流侧短路电流的工程实用计算方法,基于金属性短路故障电流通用解析式,分析了MMC-HVDC系统发生非金属性短路故障时换流站放电电流的相互抑制作用以及放电回路的耦合机理,并基于所推导的解析表达式提出了故障电流的解耦计算方法。基于PSCAD/EMTDC对MMC-HVDC系统发生非金属性短路故障工况进行仿真分析,将仿真结果与解析计算值进行对比验证。搭建数字-物理混合仿真实验模型,在数字端和物理端分别设置短路故障,对比实验值与解析计算值。验证结果表明,所提故障电流计算方法能准确地表征MMC-HVDC系统直流侧非金属性短路故障电流的演变趋势。
关键词:  模块化多电平换流器  MMC-HVDC  故障电流计算  故障特性  耦合机理  非金属性故障
DOI:10.16081/j.epae.202306016
分类号:TM713;TM721.1
基金项目:国家自然科学基金资助项目(U2066210)
Calculation method of nonmetallic short circuit fault current in DC side of MMC-HVDC system
WANG Zhuoya1, HAO Liangliang1, WANG Le1, HE Jinghan1, CHEN Zhengguang2
1.College of Electrical Engineering, Beijing Jiaotong University, Beijing 100044, China;2.State Grid Corporation of China, Beijing 100031, China
Abstract:
To explore the practical engineering calculation method of DC side short circuit current of modular multilevel converter based high voltage direct current(MMC-HVDC) system, the mutual suppression of discharge current and coupling mechanism of discharge circuit under the condition of nonmetallic short circuit fault are analyzed based on the general analytical formula of metallic short circuit fault current. And the decoupling calculation method of short circuit current is proposed based on the deduced analytical formula. The nonmetallic short circuit fault condition of MMC-HVDC system is simulated based on PSCAD/EMTDC, and the simulative results are compared with the analytical calculation values. Meanwhile, a digital-physical hybrid simulation experiment model is established, and the short circuit faults are set at the digital and the physical terminals respectively to compare the experimental values with the analytical values. The verification results indicate that the proposed short circuit current calculation method can accurately characterize the current evolution trend of nonmetallic short circuit fault current in DC side of MMC-HVDC system.
Key words:  modular multilevel converter  MMC-HVDC  fault current calculation  fault characteristics  coupling mechanism  nonmetallic fault

用微信扫一扫

用微信扫一扫