Line-line fault protection scheme of PV array based on current reverse mutation criterion of fault PV string
投稿时间:2022-09-19  修订日期:2023-06-05
查看全文(View full text)  View / Add Comment  Download PDF Reader
English Abstract:
      The fault current is small when line-line fault occurs in the photovoltaic(PV) array, and overcurrent protection cannot effectively clear the fault. A PV array line-line fault protection scheme based on the reverse mutation characteristics of PV string output current is proposed. The characteristics of the PV string’s output voltage and current under PV array line-line fault are qualitatively analyzed, which shows that the current will reversely decrease under PV array line-line fault. Then, based on the equivalent circuit model of PV string, the quantitative relationship between the output current and the number of the faulty battery is established. Setting the current reduction for one faulty battery as the threshold, a current reverse mutation criterion of fault PV string is proposed, which can effectively locate the fault string of PV array and only need to measure the output current signal of the PV string and the output voltage signal of the PV array. Meanwhile, the protection cooperation only need trip signal. The correctness of the theoretical analysis of the proposed criterion and the effectiveness of the proposed relay protection scheme are verified by time-domain simulations and field test.
作者单位
孙旻 国网江西省电力有限公司电力科学研究院江西 南昌 330096
江西省新能源电力系统运行控制重点实验室江西 南昌 330096 
曾伟 国网江西省电力有限公司电力科学研究院江西 南昌 330096
江西省新能源电力系统运行控制重点实验室江西 南昌 330096 
陈波 国网江西省电力有限公司电力科学研究院江西 南昌 330096
江西省新能源电力系统运行控制重点实验室江西 南昌 330096 
王冠南 国网江西省电力有限公司电力科学研究院江西 南昌 330096
江西省新能源电力系统运行控制重点实验室江西 南昌 330096 
彭春华 华东交通大学 电气与自动化工程学院江西 南昌 330013 
高波 华东交通大学 电气与自动化工程学院江西 南昌 330013 
English and key words:PV power generation  PV array line-line fault  fault current  reverse mutation  relay protection
基金项目:国家电网有限公司总部科技项目(5400-202323225A-1-1-ZN);江西省急需紧缺海外人才项目(20223BCJ25031)
DOI:10.16081/j.epae.202308021
Colse

用微信扫一扫

用微信扫一扫