引用本文:姜飞,涂春鸣,熊龙珠,郭祺,吴连贵.新型动态电压恢复器对短路故障电流主动调节的研究[J].电力自动化设备,2017,37(9):
JIANG Fei,TU Chunming,XIONG Longzhu,GUO Qi,WU Liangui.Active short circuit current adjustment by modified dynamic voltage restorer[J].Electric Power Automation Equipment,2017,37(9):
【打印本页】   【HTML】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 4168次   下载 1732  
新型动态电压恢复器对短路故障电流主动调节的研究
姜飞1, 涂春鸣2, 熊龙珠3, 郭祺2, 吴连贵2
1.长沙理工大学 电气与信息工程学院,湖南 长沙 410004;2.湖南大学 国家电能变换与控制工程技术研究中心,湖南 长沙 410082;3.国网张家界供电局,湖南 张家界 427000
摘要:
提出在动态电压恢复器(DVR)系统的串联逆变器交流输出端增设反并联晶闸管支路的拓扑,以实现动态电压补偿功能与故障电流限制功能。分析所提拓扑的故障电流限制功能机理,建立其运行数学模型;在限流功能动态过程分析基础上,提出一种通过调整晶闸管触发相位角的故障电流调节方法,给出限流阻抗的调节范围,从而解决限流阻抗与电网原有过流保护的配合问题;最后,采用PSCAD/EMTDC仿真软件和实验室样机,验证所提拓扑及控制方法的正确性。
关键词:  动态电压恢复器  故障限流  滤波器  多功能  主动调节
DOI:10.16081/j.issn.1006-6047.2017.09.019
分类号:TM761
基金项目:国家自然科学基金资助项目(51377051)
Active short circuit current adjustment by modified dynamic voltage restorer
JIANG Fei1, TU Chunming2, XIONG Longzhu3, GUO Qi2, WU Liangui2
1.College of Electrical and Information Engineering, Changsha University of Science & Technology, Changsha 410004, China;2.Power Conversion and Control Engineering Technology Research Center, Hunan University, Changsha 410082, China;3.State Grid Zhangjiajie Electric Power Bureau, Zhangjiajie 427000, China
Abstract:
A modified topology of DVR(Dynamic Voltage Restorer) is proposed, which has an additional bidi-rectional thyristor branch across the output terminals of series inverter to realize the functions of dynamic voltage compensation and fault-current limiting. The mechanism of its fault-current limiting is analyzed and an operating model is established, based on which, a method of fault-current adjustment by changing the firing angle of thyristor is proposed and the adjustment range of current limiting impedance is developed for its cooperation with the existing over-current protection of grid. The correctness of the proposed topology and adjustment method is verified by the simulation based on the PSCAD/EMTDC software and a lab prototype.
Key words:  dynamic voltage restorer  fault-current limiting  electric filters  multi-function  active adjustment