引用本文:杨磊,曾祥君,喻锟,余敏琪,周宁,冯光.新型谐振接地系统接地故障全补偿方法[J].电力自动化设备,2018,(11):
YANG Lei,ZENG Xiangjun,YU Kun,YU Minqi,ZHOU Ning,FENG Guang.Novel method of full compensation for grounding fault of resonant grounding system[J].Electric Power Automation Equipment,2018,(11):
【打印本页】   【HTML】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 4052次   下载 1962  
新型谐振接地系统接地故障全补偿方法
杨磊1, 曾祥君1, 喻锟1, 余敏琪1, 周宁2, 冯光2
1.长沙理工大学 智能电网运行与控制湖南省重点实验室,湖南 长沙410014;2.国网河南省电力公司电力科学研究院,河南 郑州450052
摘要:
针对传统消弧线圈无法补偿有功电流和抑制间歇性接地故障等难题,提出了一种谐振接地系统接地故障全补偿新方法。系统正常运行时,通过注入信号谐振精确测量系统对地绝缘参数,根据绝缘参数计算补偿元件值;当发生接地故障时,利用故障电流的相位选出故障相,然后在故障相的滞后相投入阻容性补偿元件,将故障相电压抑制为0,实现接地故障电流全补偿。仿真分析表明,所提方法不受过渡电阻影响,能快速抑制故障相电压,实现配电系统接地故障电流的全补偿,有效抑制间歇性接地故障,且操作简单可靠、成本低。
关键词:  谐振接地系统  单相接地故障  故障消弧  故障相电压  全补偿
DOI:10.16081/j.issn.1006-6047.2018.11.009
分类号:TM77
基金项目:国家自然科学基金资助项目(51737002);湖南省研究生科研创新项目(CX2017B480);国家电网公司科学技术项目(52170217000S)
Novel method of full compensation for grounding fault of resonant grounding system
YANG Lei1, ZENG Xiangjun1, YU Kun1, YU Minqi1, ZHOU Ning2, FENG Guang2
1.Hunan Province Key Laboratory of Smart Grids Operation and Control, Changsha University of Science and Technology, Changsha 410014, China;2.Electric Power Research Institute of State Grid Henan Electric Power Company, Zhengzhou 450052, China
Abstract:
In order to solve the problems that the traditional arc suppression coil cannot compensate the active current nor suppress the intermittent-arc grounding fault, a novel method of full compensation for grounding fault of resonant grounding system is proposed. In the normal state of resonant grounding system, the values of compensation components are calculated based on the system insulation parameters precisely measured by injecting signal resonance. When single-phase grounding fault occurs, the fault phase is selected by the phase of the fault current. Then the resistance capacitive compensation components are put into the lagging phase of the fault phase, so that the fault phase voltage can be suppressed to zero and the grounding fault current can be fully compensated. The simulative analysis shows that immune to the transition resistance, the proposed method can quickly suppress the fault phase voltage, realize full compensation of the grounding fault current for the distribution system and effectively suppress the intermittent grounding fault, meanwhile, its operation is simple and reliable, and its cost is low.
Key words:  resonant grounding system  single-phase grounding fault  arc suppression  fault phase voltage  full compensation

用微信扫一扫

用微信扫一扫