引用本文:黄伟,陈炜,吴军,刘涤尘,吴琛,程旻,陈桢.基于功率平衡控制原理的双馈风电机组辅助调频方法[J].电力自动化设备,2019,39(1):
HUANG Wei,CHEN Wei,WU Jun,LIU Dichen,WU Chen,CHENG Min,CHEN Zhen.Auxiliary frequency modulation method of DFIG-based wind turbine based on principle of power balance control[J].Electric Power Automation Equipment,2019,39(1):
【打印本页】   【HTML】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 5012次   下载 2113  
基于功率平衡控制原理的双馈风电机组辅助调频方法
黄伟1, 陈炜2, 吴军2, 刘涤尘2, 吴琛1, 程旻1, 陈桢3
1.云南电网有限责任公司,云南 昆明 650000;2.武汉大学 电气与自动化学院,湖北 武汉 430072;3.华能福州电厂,福建 福州 350000
摘要:
高比例的风电并网给电网的功率平衡与频率稳定带来了严峻的挑战,如何充分发挥变速风电机组的有功备用潜力,研究风电场快速可控的调频控制方法成为提高风电消纳能力的关键问题。提出适用于全风速工况的变速变桨距风电机组的改进型有功控制策略,有效地实现了风电场响应电网功率调度指令减载运行并提供旋转备用。考虑风电场分散接入场景,针对机组跳机和负荷脱网等可监测的、大容量的单一扰动/故障事件,基于功率平衡控制原理提出风电场的辅助调频协调控制新方法,在电网功率发生突变时,根据风电场与扰动节点的最短电气距离,合理启动和分配不同风电场的紧急功率控制容量。仿真结果表明,所设计的风电场有功-频率控制方案能从降低暂态频率偏差幅值及减小频率恢复时间两方面,有效地提升系统发生扰动后的频率稳定性。
关键词:  变速变桨距风电机组  功率平衡控制  紧急功率控制  电气距离  有功-频率控制  调频
DOI:10.16081/j.issn.1006-6047.2019.01.010
分类号:TM614
基金项目:云南电网有限责任公司科技项目(风、光新能源调频及调压协调控制技术研究)(0560002018030301XT00120)
Auxiliary frequency modulation method of DFIG-based wind turbine based on principle of power balance control
HUANG Wei1, CHEN Wei2, WU Jun2, LIU Dichen2, WU Chen1, CHENG Min1, CHEN Zhen3
1.Yunnan Power Grid Co.,Ltd.,Kunming 650000, China;2.School of Electrical Engineering and Automation, Wuhan University, Wuhan 430072, China;3.Huaneng Fuzhou Power Plant, Fuzhou 350000, China
Abstract:
The high proportion of grid-connected wind power brings severe challenges of power balance and frequency stability to the power grid. How to make full use of the active reserve of variable-speed wind turbines and study the fast-flexible frequency modulation control method of wind farm become the key issues to improve the wind power consumption capacity. An improved active power control strategy for variable-speed variable-pitch wind turbines under full-wind speed condition is proposed, which can make the wind farm realize load shedding to response to the power dispatching order and provide active power reserve effectively. Considering the decentralized accessing scenario of wind farms and aiming at the monitorable, large-capacity single disturbance or fault event such as generator trip, load off-network, and so on, a new coordinated auxiliary frequency modulation method is proposed based on the principle of power balance control. When the power of the grid changes suddenly, the emergency power support capacity of different wind farms are started and allocated reasonably according to the shortest electrical distance between the wind farms and the disturbance node. Simulative results show that the designed power-frequency control strategy can effectively improve the frequency stability of the power grid after the disturbance from two aspects of reducing the amplitude of transient frequency deviation and the frequency recovery time.
Key words:  variable-speed variable-pitch wind turbine  power balance control  emergency power control  electrical distance  active power-frequency control  frequency regulation