引用本文:程建材,康龙云,胡毕华,冯元彬.三电平并网逆变器恒定开关频率的模型预测控制[J].电力自动化设备,2019,39(5):
CHENG Jiancai,KANG Longyun,HU Bihua,FENG Yuanbin.Model predictive control with constant switching frequency of three-level grid-connected inverter[J].Electric Power Automation Equipment,2019,39(5):
【打印本页】   【HTML】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 4020次   下载 2019  
三电平并网逆变器恒定开关频率的模型预测控制
程建材1,2, 康龙云1,2, 胡毕华1,2, 冯元彬1,2
1.华南理工大学电力学院,广东广州510640;2.华南理工大学广东省绿色能源技术重点实验室,广东广州510640
摘要:
传统的有限控制集模型预测控制存在开关频率不固定的缺点,这给并网逆变器输出滤波器的设计带来了很大的困难。针对这个问题,提出了一种三电平并网逆变器恒定开关频率的模型预测控制策略。该控制策略将预测最优开关序列控制用于三电平并网逆变器中,并对其寻优方式进行改进。改进的方式是通过找出使目标函数最小的中心矢量来对最优开关序列所在的小扇区进行定位。仿真和实验结果表明,所提控制策略不仅能够在实现定频控制的基础上有效减少计算量,而且具有良好的静态和动态性能。
关键词:  三电平并网逆变器  模型预测控制  恒定开关频率  开关序列  中心矢量
DOI:10.16081/j.issn.1006-6047.2019.05.025
分类号:TM464
基金项目:广东省科技发展专项基金资助项目(2017B010120001)
Model predictive control with constant switching frequency of three-level grid-connected inverter
CHENG Jiancai1,2, KANG Longyun1,2, HU Bihua1,2, FENG Yuanbin1,2
1.School of Electric Power, South China University of Technology, Guangzhou 510640, China;2.Key Laboratory of Clean Energy Technology of Guangdong Province, South China University of Technology, Guangzhou 510640, China
Abstract:
Traditional FCS-MPC(Finite Control Set Model Predictive Control) cannot provide a constant switching frequency, which brings huge difficulties to the design of output filter. To address this issue, a CSF-MPC(Constant Switching Frequency Model Predictive Control) for three-level grid-connected inverters is proposed. The proposed algorithm applies the predicted optimal switch sequence control to three-level grid-connected inverters, and improves its optimization strategy. This improved method is to locate the small sector where the optimal switching sequence is located by searching the center vector that minimizes the objective function. The simulative and experimental results show that the proposed strategy can not only provide fixed frequency with reduced computation cost, but also exhibit satisfactory static and dynamic performance.
Key words:  three-level grid-connected inverter  model predictive control  constant switching frequency  switching sequence  center vector

用微信扫一扫

用微信扫一扫