引用本文:褚飞航,黄虎,彭在兴,刘定新.252 kV断路器分合闸线圈在环境因素下的劣化规律研究[J].电力自动化设备,2021,41(2):
CHU Feihang,HUANG Hu,PENG Zaixing,LIU Dingxin.Study on degradation of 252 kV circuit breaker’s opening/closing coil under environmental factors[J].Electric Power Automation Equipment,2021,41(2):
【打印本页】   【HTML】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 10979次   下载 1738  
252 kV断路器分合闸线圈在环境因素下的劣化规律研究
褚飞航1, 黄虎1, 彭在兴2, 刘定新3
1.中国舰船研究设计中心,湖北 武汉 430064;2.南方电网科学研究院有限责任公司,广东 广州 510000;3.西安交通大学 电气工程学院,陕西 西安 710049
摘要:
高压断路器分合闸线圈在长期运行条件下,会受到温度、湿度、盐雾等环境因素的影响,其性能也会发生相应的劣化。采用湿热试验考察温度、湿度对252 kV断路器分合闸线圈的影响,采用交变盐雾试验考察温湿度及盐雾对252 kV断路器分合闸线圈的综合影响,研究了分合闸线圈在相应试验条件下的劣化情况以及分合闸线圈电流的变化情况。研究结果表明,在湿热环境下,252 kV断路器的分合闸线圈性能的劣化是一个突变过程,无法通过分合闸线圈电流进行反映;在盐雾环境下,252 kV断路器的分合闸线圈性能的劣化是一个非线性的加速过程。
关键词:  高压断路器  分合闸线圈  运行可靠性  湿热试验  交变盐雾试验
DOI:10.16081/j.epae.202011029
分类号:TM561
基金项目:
Study on degradation of 252 kV circuit breaker’s opening/closing coil under environmental factors
CHU Feihang1, HUANG Hu1, PENG Zaixing2, LIU Dingxin3
1.China Ship Development and Design Center, Wuhan 430064, China;2.Electrical Power Research Institute of CSG, Guangzhou 510000, China;3.College of Electrical Engineering, Xi’an Jiaotong University, Xi’an 710049, China
Abstract:
Under long-term operating conditions, the performance of opening/closing coil of high voltage circuit breakers degrades due to the environmental factors such as temperature, humidity and salt spray. The damp heat test is used to simulate the effects of temperature and humidity on the opening/closing coil of 252 kV circuit breaker, and the alternating salt spray test is used to simulate the combined effects of temperature, humidity and salt spray on the opening/closing coil of 252 kV circuit breaker. The degradation of the opening/closing coil under the corresponding conditions and the change of the opening/closing coil currents are studied. The study results show that the degradation of 252 kV circuit breaker’s opening/closing coil under hot and humid environment is a process of rapid change, which cannot be reflected by the opening/closing coil currents, and the degradation of 252 kV circuit breaker’s opening/closing coil under salt spray environment is a nonlinear acceleration process.
Key words:  HV circuit breaker  opening/closing coil  operation reliability  damp heat test  alternating salt spray test