引用本文:王阳光,张孝军,徐宇新,黄勇,吴宇奇,叶雨晴,马啸,王子璇,李正天.电流控制型与功率控制型分布式电源并存场景下过欠电压与过欠频率的检测盲区分析[J].电力自动化设备,2021,41(4):
WANG Yangguang,ZHANG Xiaojun,XU Yuxin,HUANG Yong,WU Yuqi,YE Yuqing,MA Xiao,WANG Zixuan,LI Zhengtian.Non-detection zone analysis on OUV and OUF under co-existence scenario of current control and power control DG[J].Electric Power Automation Equipment,2021,41(4):
【打印本页】   【HTML】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 10582次   下载 1714  
电流控制型与功率控制型分布式电源并存场景下过欠电压与过欠频率的检测盲区分析
王阳光1, 张孝军1, 徐宇新1, 黄勇1, 吴宇奇2, 叶雨晴2, 马啸2, 王子璇2, 李正天2
1.国网湖南省电力有限公司,湖南 长沙 410004;2.华中科技大学 强电磁工程与新技术国家重点实验室,湖北 武汉 430074
摘要:
目前孤岛检测研究中鲜有针对不同控制策略并存时被动法检测性能的研究分析,选取过欠电压检测法与过欠频率检测法,面向电流控制策略与功率控制策略并存场景,通过求取其检测盲区解析解并分析可得,负荷品质因数和负荷消耗无功与有功的比值只影响过欠频率检测法检测盲区,不同控制型逆变器输出有功与负荷消耗有功的比值主要影响过欠电压检测法检测盲区,同时并存场景下与单一控制策略下的检测盲区存在显著差别。
关键词:  微电网  电流控制策略  功率控制策略  过欠电压  过欠频率  检测盲区
DOI:
分类号:
基金项目:国家自然科学基金面上资助项目(51877088);国网湖南省电力有限公司科技项目(5216A018007W)
Non-detection zone analysis on OUV and OUF under co-existence scenario of current control and power control DG
WANG Yangguang1, ZHANG Xiaojun1, XU Yuxin1, HUANG Yong1, WU Yuqi2, YE Yuqing2, MA Xiao2, WANG Zixuan2, LI Zhengtian2
1.State Grid Hunan Electric Power Co.,Ltd.,Changsha 410004, China;2.State Key Laboratory of Advanced Electromagnetic Engineering and Technology, Huazhong University of Science and Technology, Wuhan 430074, China
Abstract:
In view of the problems that the detection performance analysis of passive methods are rarely studied in islanding detection research when different control strategies coexist, facing the co-existence of current control strategy and power control strategy, the non-detection zone of the over/under voltage detection method and the over/under frequency detection method are analyzed. The non-detection zone expression is obtained by solving analytical solution and the conclusions are depicted as follows: the load quality factor and the ratio of reactive power to active power consumed by load only affect the non-detection zone of over/under frequency detection method, and the ratio of active power generated by inverters to active power consumed by load under different control strategies mainly affect the non-detection zone of over/under voltage detection method. Simultaneously, there are significant differences between the non-detection zone in the different control strategies coexisting scenario and the single control strategy scenario.
Key words:  microgrid  current control strategy  power control strategy  over/under voltage  over/under frequency  non-detection zone

用微信扫一扫

用微信扫一扫