引用本文:宋国兵,侯俊杰,郭冰,王婷,常仲学,沈冰.计及主动故障限流策略的柔性直流电网纵联保护[J].电力自动化设备,2021,41(4):
SONG Guobing,HOU Junjie,GUO Bing,WANG Ting,CHANG Zhongxue,SHEN Bing.Pilot protection of flexible DC grid considering active fault current limiting strategy[J].Electric Power Automation Equipment,2021,41(4):
【打印本页】   【HTML】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 3719次   下载 1660  
计及主动故障限流策略的柔性直流电网纵联保护
宋国兵1, 侯俊杰1, 郭冰1, 王婷1, 常仲学1, 沈冰2
1.西安交通大学 电气工程学院,陕西 西安 710049;2.国网上海市电力科学研究院,上海 200437
摘要:
针对传统直流保护原理应用于柔性直流电网中存在可靠性降低、灵敏度下降的问题,提出计及换流器主动故障限流策略的柔性直流电网纵联保护原理。分析了故障电流在换流器电容放电阶段和换流器主动故障限流阶段的极性特征,进一步构造了改进型故障电流极性特征序列,引入基于斯皮尔曼相关性系数的电流波形特征判别方法,实现柔性直流电网故障区域判别。仿真结果表明,所提保护原理在换流器的电容放电阶段和换流器主动故障限流阶段均能识别出柔性直流电网故障区域,具备较高的可靠性和灵敏度。
关键词:  柔性直流电网  主动故障限流策略  相关性判别  直流保护  继电保护
DOI:
分类号:
基金项目:国家自然科学基金联合基金重点支持项目(U1766209);国家电网公司总部科技项目(52170218000M, 52094020006U)
Pilot protection of flexible DC grid considering active fault current limiting strategy
SONG Guobing1, HOU Junjie1, GUO Bing1, WANG Ting1, CHANG Zhongxue1, SHEN Bing2
1.School of Electrical Engineering, Xi’an Jiaotong University, Xi’an 710049, China;2.State Grid Shanghai Electric Power Research Institute, Shanghai 200437, China
Abstract:
In view of the problems of low reliability and sensitivity when the traditional DC protection principle is applied to flexible DC grid, the pilot protection of flexible DC grid considering active fault current limiting strategy of converter is proposed. The polarity characteristics of fault current in the capacitor discharge stage and active fault current limiting stage of converter are analyzed. Then the improved polarity sequence of fault current is constructed, and the current waveform identification method based on Spearman correlation coefficient is introduced to realize the fault area identification of flexible DC grid. The simulative results show that the proposed protection principle can identify the fault area of flexible DC grid in the capacitor discharge stage and active fault current limiting stage of converter, and has high reliability and sensitivity.
Key words:  flexible DC grid  active fault current limiting strategy  correlation discrimination  DC protection  relay protection

用微信扫一扫

用微信扫一扫