引用本文:董芷函,王国腾,徐政,李建华,丁浩寅.白鹤滩—江苏特高压混合级联直流系统运行特性分析方法[J].电力自动化设备,2022,42(6):
DONG Zhihan,WANG Guoteng,XU Zheng,LI Jianhua,DING Haoyin.Operation characteristic analysis method of Baihetan-Jiangsu hybrid cascaded UHVDC system[J].Electric Power Automation Equipment,2022,42(6):
【打印本页】   【HTML】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 2647次   下载 1090  
白鹤滩—江苏特高压混合级联直流系统运行特性分析方法
董芷函1, 王国腾1, 徐政1, 李建华2, 丁浩寅2
1.浙江大学 电气工程学院,浙江 杭州 310027;2.国家电网华东电力调控中心,上海 200120
摘要:
白鹤滩—江苏特高压混合级联直流系统逆变侧由电网换相换流器(LCC)和模块化多电平换流器(MMC)串联组成。为保证混合级联直流系统投运后安全稳定运行,从混合级联直流系统稳态响应特性、逆变侧LCC换流母线电压稳定性、MMC暂时过电压估算以及逆变站出线热稳裕度计算4个方面出发,提出了一种混合级联直流系统运行特性分析方法。仿真结果表明,所提方法可以快速、准确分析混合级联直流系统运行特性,定位系统运行薄弱环节。根据分析结果:部分工况下白鹤滩—江苏特高压混合级联直流系统的稳态响应特性较差,功率传输能力降低;交流短路故障下,MMC存在暂时过电压问题,从而影响白鹤滩—江苏特高压混合级联直流系统的正常运行。
关键词:  电网换相换流器  模块化多电平换流器  混合级联直流系统  响应特性  暂时过电压
DOI:10.16081/j.epae.202203022
分类号:TM74;TM721.1
基金项目:国家电网华东分部科技项目(SGHD0000DKJS2000087)
Operation characteristic analysis method of Baihetan-Jiangsu hybrid cascaded UHVDC system
DONG Zhihan1, WANG Guoteng1, XU Zheng1, LI Jianhua2, DING Haoyin2
1.College of Electrical Engineering, Zhejiang University, Hangzhou 310027, China;2.State Grid East China Electric Power Control Center, Shanghai 200120, China
Abstract:
The inverter side of Baihetan-Jiangsu hybrid cascaded UHVDC(Ultra High Voltage Direct Current) system is composed of LCC(Line Commutated Converter) and MMC(Modular Multilevel Converter) in series. In order to ensure the safe and stable operation of the hybrid cascaded DC system, an operation characteris-tic analysis method of the hybrid cascaded DC system is proposed from the four aspects of the steady-state response characteristics of the hybrid cascaded DC system, the voltage stability of commutation bus of inverter-side LCC, the estimation of MMC temporary overvoltage, and the thermal stability margin calculation of inverter station outlines. The simulative results show that the proposed method can quickly and accurately analyze the operation characteristics of the hybrid cascaded DC system and locate the weak links of the system. According to the analysis results, the steady-state response characteristics of the Baihetan-Jiangsu hybrid cascaded UHVDC system are poor and the power transmission capacity is reduced under certain operating conditions. Under AC short circuit faults, the MMC has the problem of temporary overvoltage, which affects the normal operation of the Baihetan-Jiangsu hybrid cascaded UHVDC system.
Key words:  LCC  MMC  hybrid cascaded DC system  response characteristics  temporary overvoltage