摘要: |
首先对一次110kV/10kV,31500kV·A变压器的轻微匝间故障进行了分析,继而导出对变压器轻微匝间短路的实用计算方法。最后根据轻微故障的特点提出对变压器比率差动继电器通用特性选择的建议,供同仁参考。 |
关键词: 变压器 匝间故障 差动保护 |
DOI: |
分类号:TM403.5 |
基金项目: |
|
Transformer Protection for Low Percentage Interturn Faults |
Zhu Shengshi
|
Abstract: |
The analysis of an interturn fault about one percentage turns is introduced and a calculating formula for estimating the interturn fault current of the transformer is derived.According to the calculation result and features of low percentage interturn fault,the general characteristic selection for percentage differential relay of transformer is suggested. |
Key words: Transformer,Interturn faults,differential protection |