引用本文: | 刘洪志,刘金涛,王玉林,张启春.300MW发电机基波定子接地保护定值分析[J].电力自动化设备,2004,(5):67-68,71 |
| .Setting value analysis for 300 MW generator stator grounding protection[J].Electric Power Automation Equipment,2004,(5):67-68,71 |
|
|
摘要: |
现场运行中定子接地保护误发信号时有发生,一些单位为使保护运行可靠,从而大幅度提高定值。通过计算及试验指出,合理调整消弧线圈与系统参数的配合,可以降低保护定值,提高运行可靠性。 |
关键词: 发电机 定子接地 消弧线圈 定值 |
DOI: |
分类号:TM31 TM772 |
基金项目: |
|
Setting value analysis for 300 MW generator stator grounding protection |
LIU Hong-zhi1 LIU Jin-tao1 WANG Yu-lin1 ZHANG Qi-chun2
|
Abstract: |
In site operation,stator grounding protection often gives false signal,therefore some units raise the setting value greatly for the dependability of protection. It is pointed out that the proper adjustment of arc suppression coil and coordination of system parameters may reduce the setting values and improve the running reliability. |
Key words: generator,stator grounding,arc suppression coil,setting value |