引用本文: | 杨佳,杨洪涛,于跃海,谢新华.基于Hypersim实时仿真系统的备自投装置测试[J].电力自动化设备,2008,(4):117-121 |
| .Automatic switchover device test based on Hypersim real-time simulation system[J].Electric Power Automation Equipment,2008,(4):117-121 |
|
|
摘要: |
针对目前的备自投装置测试,只能进行开环测试,无法考虑装置在系统中实际运行情况,介绍了一种基于Hypersim实时仿真系统的备自投装置的试验研究方法。为验证备自投装置的实际工作情况,在Hypersim中建立了电网的仿真系统,并将被测装置所需要的模拟信号输出,装置的控制信号再返回Hypersim中,从而形成备自投装置的闭环测试环境。按照试验要求进行了各项试验,对测试输出波形做了理论分析,从仿真结果可知,所介绍的方法用于备自投装置试验是切实可行的。 |
关键词: Hypersim实时仿真系统,NSR640R备自投,电网 |
DOI: |
分类号:TM732 |
基金项目: |
|
Automatic switchover device test based on Hypersim real-time simulation system |
YANG Jia YANG Hongtao YU Yuehai XIE Xinhua
|
Abstract: |
To test the performance of automatic switchover device in real operational conditions than the pure open - loop control,a test method based on Hypersim real - time simulation system is presented. The simulation system of a real power grid is built up in Hypersim,which outputs the simulative signals needed by the automatic switchover device and inputs the control signals from device to form a close - loop test environment. Different kinds of test are carried out and the corresponding output waveforms are analyzed. The simulation results show that the proposed test method is feasible. |
Key words: Hypersim real - time simulation system,NSR640R automatic switchover device,power grid |