Improvement and checkout of remote control circuit for breaker |
PAN Pengfei, WANG Hongzhe, LI Jian, HAN Guangwei
|
Dalian Power Supply Company,Dalian 116001,China
|
Abstract: |
New functions are added to remote control circuit,such as manual handle,synchronous switch-on enabling,synchronous switch-on disabling,error-prevention electronic lock and remote control enabling,and their operating principles and features are analyzed. The checkout scheme for synchronous switch-on function/accuracy,voltage blocking,differential voltage blocking,differential frequency blocking and differential phase-angle blocking is proposed. The statistics of remote control operations in four 220 kV substations for nearly one year show that,the new remote control circuit functions properly,without any misoperation,verifying the reliability of improvement and the effectiveness of checkout scheme. |