引用本文:霍思敏,汤吉鸿,徐宇新,李 勃,刘海峰.一起复杂事故的保护动作行为分析[J].电力自动化设备,2012,32(3):
HUO Simin,TANG Jihong,XU Yuxin,LI Bo,LIU Haifeng.Analysis of protection behavior in a complex accident[J].Electric Power Automation Equipment,2012,32(3):
【打印本页】   【HTML】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 4930次   下载 63  
一起复杂事故的保护动作行为分析
霍思敏1, 汤吉鸿1, 徐宇新1, 李 勃1, 刘海峰2
1.湖南省电力公司调度通信局,湖南 长沙 410007;2.湖南省电力科学研究院,湖南 长沙 410007
摘要:
某220 kV变电站发生了一起连续多次故障,保护误动、电压互感器(TV)断线、保护闭锁与间隙击穿等相互交织的复杂事故。在缺乏录波数据的情况下,采用相量分析的方法,分析了第1次故障时变压器差动保护误动的原因,指导了变压器差动保护电流回路故障点的查找;通过分析故障录波数据,分析了第2次故障时变压器中压侧后备保护与110 kV线路保护同时动作的原因,准确地判断出相邻变电站发生了变压器间隙击穿的情况。提出了主变中压侧复压方向过流保护应与该侧出线TV断线过流保护在时间上取得配合,就可避免主变中压侧复压过流保护越级动作的建议。
关键词:  事故  变电站  相量分析  变压器  差动保护  误动
DOI:
分类号:
基金项目:
Analysis of protection behavior in a complex accident
HUO Simin1, TANG Jihong1, XU Yuxin1, LI Bo1, LIU Haifeng2
1.Dispatch and Communication Bureau of Hunan Power Corporation,Changsha 410007,China;2.Hunan Power Science Research Institute,Changsha 410007,China
Abstract:
A complex accident occurred in a 220 kV substation is analyzed:protection maloperation,PT(Potential Transformer) line-break,protection-blocking and clearance breakdown. As there is no recorded fault data,the vector analysis is used to analyze the protection maloperation and the fault point in the current circuit of transformer differential protection is found. Why the transformer back-up protection and 110 kV line protection operate simultaneously is analyzed based on the recorded fault data and the transformer clearance breakdown in adjacent substation is accurately detected. It is pointed out that the proper matching of setting time between the over-current protection at mid-voltage side of main transformer and the PT line-break over-current protection may avoid the maloperation of over-current protection at mid-voltage side of main transformer.
Key words:  electric accidents  electric substations  phasor analysis  electric transformers  differential protection  maloperation