引用本文:雷 一,赵争鸣,鲁思兆.LCL滤波的光伏并网逆变器有源阻尼与无源阻尼混合控制[J].电力自动化设备,2012,32(11):
LEI Y,ZHAO Zhengming,LU Sizhao.Hybrid control of active and passive damping for grid-connected PV inverter with LCL filter[J].Electric Power Automation Equipment,2012,32(11):
【打印本页】   【HTML】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 4701次   下载 44  
LCL滤波的光伏并网逆变器有源阻尼与无源阻尼混合控制
雷 一, 赵争鸣, 鲁思兆
清华大学 电力系统与发电设备控制与仿真国家重点实验室,北京 100084
摘要:
通过建立LCL滤波的光伏并网电流控制内环模型,就电网电感对谐振频率、无源阻尼效果和电容电流反馈的有源阻尼效果三者的影响进行了分析。结果表明,电网电感能降低谐振频率,增强有源阻尼效果,削弱无源阻尼效果。结合有源阻尼受延迟等控制非理想因素影响较大、而无源阻尼不受此影响的特点提出了一种采用有源阻尼与无源阻尼相结合的混合阻尼策略,它对于电网电感和控制延迟都具有良好的适应性。混合阻尼设计中以阻尼系数为对象,以阻尼系统对电网电感的适应能力为设计目标,计算和校验电流反馈系数和阻尼电阻取值,给出了具体设计方法。设计实例的仿真和实验结果证明,该方法设计的阻尼可以稳定运行,并对弱电网具有良好的适应性。
关键词:  光伏发电  LCL滤波器  有源阻尼  无源阻尼  逆变器
DOI:
分类号:
基金项目:国家自然科学基金重点资助项目(50737002);台达环境与教育基金会电力电子科教发展计划重大项目(DREM-200902)
Hybrid control of active and passive damping for grid-connected PV inverter with LCL filter
LEI Y, ZHAO Zhengming, LU Sizhao
State Key Lab of Control and Simulation of Power System & Generation Equipment,Tsinghua University,Beijing 100084,China
Abstract:
The inner current control loop of PV inverter with LCL filter is modeled and the impact of grid inductance on the active damping and passive damping of resonance frequency and capacitive current is analyzed,which shows that,the grid inductance may decrease the resonance frequency,enhance the active damping and weaken the passive damping. Based on the fact that the active damping is easily affected by the nonideal control factors while the passive damping is immune to them,a hybrid control scheme of active and passive damping is proposed,which has better adaptability to grid inductance and control delay. The scheme design takes the hybrid damping coefficient as its design object and the adaptability of damping system to grid inductance as its design objective to calculate and verify the current feedback coefficient and damping resistance. Detailed design process is given. The simulative and experimental results show that the damping system designed stabilizes the operation,having better adaptability to weak grid.
Key words:  PV generation  LCL filter  active damping  passive damping  electric inverters

用微信扫一扫