引用本文:汤大海,严国平,易 新.220 kV线路距离保护在V / X接线牵引变压器短路时的测量阻抗分析[J].电力自动化设备,2013,33(2):
TANG Dahai,YAN Guoping,YI Xin.Measured impedance of 220 kV line protection during short circuit of traction transformer with V/ X connection[J].Electric Power Automation Equipment,2013,33(2):
【打印本页】   【HTML】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 8916次   下载 1714  
220 kV线路距离保护在V / X接线牵引变压器短路时的测量阻抗分析
汤大海1, 严国平2, 易 新2
1.镇江供电公司,江苏 镇江 212001;2.江苏省电力公司,江苏 南京 210024
摘要:
基于V/V接线牵引变压器低压侧短路时短路电流分析,推导出该短路情况下,电源侧变电所220 kV线路距离保护相间阻抗元件和接地阻抗元件的测量阻抗计算式,并根据计算式给出了V/V接线牵引变压器低压侧两相短路和三相短路时的220 kV线路距离保护的最小测量阻抗。对V/X接线牵引变压器的各种短路类型进行了分析,发现只要将牵引变压器等值参数Z变为Z′或Z ″,V/V接线牵引变压器短路时对220 kV 线路距离保护的测量阻抗的分析,同样适用于V/X接线牵引变压器短路情况。通过仿真实验,验证了所推导的测量阻抗计算式的正确性,其适用于V/X接线牵引变压器。最后基于上述理论分析和仿真实验结果,给出了220 kV线路距离保护整定计算公式和注意事项。
关键词:  220kV线路距离保护  牵引变压器  V/X接线  短路电流  测量阻抗
DOI:
分类号:
基金项目:
Measured impedance of 220 kV line protection during short circuit of traction transformer with V/ X connection
TANG Dahai1, YAN Guoping2, YI Xin2
1.Zhenjiang Power Company,Zhenjiang 212001,China;2.Jiangsu Provincial Power Company,Nanjing 210024,China
Abstract:
The low voltage side short circuit current of traction transformer with V/V connection is analyzed,based on which,the formulas for calculating the measured impedance of inter-phase impedance element and grounding impedance element of 220 kV line distance protection are deduced. The minimal measured impedances of 220 kV line distance protection are thus calculated for two-phase and three-phase short circuits at low voltage side. Different short circuit kinds of traction transformer with V/X connection are analyzed and it is found that,the measured impedance of 220 kV line distance protection analyzed for the LV-side short circuit current of traction transformer with V/V connection is applicable to that with V/X connection as long as the equivalent parameter Z is replaced by Z′ or Z ″,which is verified by simulative experiment. The formulas for calculating the settings of 220 kV line distance protection are given with notes.
Key words:  220 kV line distance protection  traction transformer  V/X wiring  electric short circuit currents  measured impedance