引用本文:黎东祥,王渝红,丁理杰,李兴源,戴寒光,宿国良.基于双12脉动阀组共同控制的特高压单阀组投退策略[J].电力自动化设备,2014,34(4):
LI Dongxiang,WANG Yuhong,DING Lijie,LI Xingyuan,DAI Hanguang,SU Guoliang.Blocking and deblocking strategy of single UHVDC converter group under joint control mode of dual 12-pulse converter groups[J].Electric Power Automation Equipment,2014,34(4):
【打印本页】   【HTML】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 10902次   下载 1960  
基于双12脉动阀组共同控制的特高压单阀组投退策略
黎东祥1,2, 王渝红1,2, 丁理杰3, 李兴源1,2, 戴寒光1,2, 宿国良1,2
1.四川大学 电气信息学院,四川 成都 610065;2. 四川电力科学研究院,四川 成都 610072;3.四川电力科学研究院,四川 成都 610072
摘要:
借助PSCAD/EMTDC 程序研究了特高压直流输电系统双12脉动阀组共同控制方式下的单阀组投入和退出策略,分析了阀组触发角、触发脉冲、旁路开关、旁通对和在线调整控制器相关参数之间的顺序控制、时序配合。仿真结果表明:在双12脉动阀组共同控制方式下,单阀组投入宜采用小触发角解锁方式,解除触发角限制后串入限速模块和限幅模块可以改善投入过程中的直流运行参数动态响应特性;单阀组退出时,触发角按一定速率调整到90°,并投旁通对可加速退出过程。实例仿真表明所提控制策略能够满足特高压直流单阀组投退的要求。
关键词:  特高压输电  直流输电  共同控制  12脉动阀组  控制
DOI:
分类号:
基金项目:国家自然科学基金资助项目(51037003);四川省电力公司科技项目
Blocking and deblocking strategy of single UHVDC converter group under joint control mode of dual 12-pulse converter groups
LI Dongxiang,WANG Yuhong,DING Lijie,LI Xingyuan,DAI Hanguang,SU Guoliang
1.School of Electrical Engineering and Information,Sichuan University,Chengdu 610065,China;2.Sichuan Electric Power Research Institute,Chengdu 610072,China
Abstract:
The blocking and deblocking strategy of single converter group under the joint control mode of dual 12-pulse converter groups is studied with PSCAD/EMTDC for UHVDC power transmission system. The sequential control and timing coordination of firing angle,ignition pulse,bypass switch,bypass pair and online controller parameter adjustment are analyzed. Simulative results show that,the deblocking of single converter group should adopt small firing angle under the joint control mode of dual 12-pulse converter groups and the rate limiter and value limiter should be added in series after the firing angle limiter is disabled to improve the dynamic performance of DC operating parameters during the deblocking;while during its blocking,the firing angle should be adjusted to 90° at a certain rate and the bypass pair should be put into operation to speed up the blocking process. Case studies show that the proposed strategy meets the requirements of UHVDC single converter group blocking and deblocking operations.
Key words:  UHV power transmission  DC power transmission  joint control  12-pulse converter groups  control