引用本文:魏本刚,吴楠楠,任晓明,戴明秋.基于有限体积法的分体式冷却变压器热学三维仿真技术[J].电力自动化设备,2018,(2):
WEI Bengang,WU Nannan,REN Xiaoming,DAI Mingqiu.Three dimensional simulation technology of cooling separated transformer based on finite volume method[J].Electric Power Automation Equipment,2018,(2):
【打印本页】   【HTML】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 4614次   下载 1507  
基于有限体积法的分体式冷却变压器热学三维仿真技术
魏本刚1,2, 吴楠楠3, 任晓明3, 戴明秋4
1.国网上海市电力公司电力科学研究院,上海200437;2.上海赛璞乐电力科技有限公司,上海200437;3.上海电机学院电气学院,上海201306;4.上海交通大学电气与电子工程学院,上海200240
摘要:
变压器分体式冷却系统与常规冷却方式的散热器安装位置与安装方式均差别较大。由于分体式冷却系统的特殊性,在进行仿真模型研究时参数制定和模型搭建较复杂,目前对其进行热学仿真的研究较少,且仿真准确性难以验证,需要开展更加深入的仿真研究和试验比对工作。对改造的10 kV油浸式变压器进行分体式冷却方式下的模拟试验,基于模拟试验变压器及分体式冷却器的设置建立了变压器分体式冷却系统的三维流-固-热耦合仿真计算模型,采用有限体积法求解出变压器及分体式冷却器的温度场分布,得到分体式冷却器在不同布置方式下的绕组热点温度。将仿真计算结果与试验数据、IEEE导则计算结果进行比对,结果显示,仿真得到的绕组热点温升、顶层油温升的误差比IEEE导则计算结果的误差分别减小了16.6、15.15 K,验证了该仿真模型的准确性和工程实用性。分析显示,试验模型散热器中心高度增加2 m,热点温度降低了7.9 K;散热器与变压器水平距离缩短3.5 m,热点温度上升了4.1 K,从而获得了分体式冷却布置方式对变压器热点温度变化趋势的影响。
关键词:  油浸式变压器  分体冷却  流-固-热耦合仿真  三维温度场
DOI:10.16081/j.issn.1006-6047.2018.02.023
分类号:TM41
基金项目:
Three dimensional simulation technology of cooling separated transformer based on finite volume method
WEI Bengang1,2, WU Nannan3, REN Xiaoming3, DAI Mingqiu4
1.Electric Power Research Institute, SGEPC, Shanghai 200437, China;2.Shanghai SEPRI Power Technology Co.,Ltd.,Shanghai 200437, China;3.Shanghai College of Electrical Engineering, Shanghai 201306, China;4.Shanghai Jiao Tong University, Shanghai 200240, China
Abstract:
There are obvious differences between separated cooling system and conventional cooling system of transformers in the radiator mounting position and installation modes. Due to the specific characteristics of separated coo-ling system, the parameter setting and model construction in simulation research are complicated, so the researches on thermal simulation for separated cooling system is few, and it is difficult to identify the accuracy of simulation. More deeper simulation research and trial comparisons are needed. The separated cooling experiments of a 10 kV oil-immersed transformer under three different layouts of transformer and radiator are carried out. The three dimensional fluid-structural-thermal coupling simulation model of the tested transformer and its panel-type radiator is established based on the layout of the transformer and the radiator. The finite volume method is adopted to solve the temperature field distribution of transformer and the transformer and its panel-type radiator, the hot spot temperature of transformer is obtained. The simulative results are compared with the experimental data and IEEE standard calculation results, which shows that the errors of winding temperature rise and top oil temperature rise obtained by simulation are respectively 16.6 K and 15.15 K lower than those of IEEE standard calculation results. It verifies the accuracy and engineering practicability of the proposed simulation model. The analysis show that if the height of radiator center in the tested model is increased by 2 meters, the hot spot temperature will be decreased by 7.9 K, and if the horizontal distance between radiator and transformer is shortened by 3.5 meters, the hot spot temperature will be increased by 4.1 K, which shows the effect of the layout of separated cooling system on hot spot temperature of transformer.
Key words:  oil-immersed transformers  separated cooling unit  fluid-structural-thermal coupling simulation  three-dimensional temperature field