引用本文:程孟晗,褚宁,梁睿,彭楠.基于多模量行波分量相位关系的输电线路单相接地故障定位[J].电力自动化设备,2018,(10):
CHENG Menghan,CHU Ning,LIANG Rui,PENG Nan.Single-phase grounding fault location based on phase relation between multi-modulus traveling waves for transmission line[J].Electric Power Automation Equipment,2018,(10):
【打印本页】   【HTML】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 3919次   下载 1644  
基于多模量行波分量相位关系的输电线路单相接地故障定位
程孟晗1, 褚宁1,2, 梁睿1,2, 彭楠1,2
1.中国矿业大学电气与动力工程学院,江苏徐州221116;2.江苏省煤矿电气与自动化工程实验室,江苏徐州221116
摘要:
为了充分利用模量行波首波头相位信息,克服传统模量行波首波头辨识方法的误差,基于模量行波在输电线路上传播时的畸变特性和色散效应,提出利用双端测量点零模和线模电压行波首波头中同一高频分量相位关系进行单相接地故障定位。所提方法无需双端精确同步,也不依赖于模量行波到达时刻和波速信息。利用PSCAD搭建输电线路模型并进行故障仿真,仿真结果表明了所提方法的有效性与可靠性。
关键词:  模量行波  畸变  相位关系  输电线路  故障定位
DOI:10.16081/j.issn.1006-6047.2018.10.027
分类号:TM77
基金项目:国家自然科学基金资助项目(51504253);江苏省自然科学基金资助项目(BK20161185);国家级大学生科研训练计划(201710290047)
Single-phase grounding fault location based on phase relation between multi-modulus traveling waves for transmission line
CHENG Menghan1, CHU Ning1,2, LIANG Rui1,2, PENG Nan1,2
1.School of Electrical and Power Engineering, China University of Mining and Technology, Xuzhou 221116, China;2.Jiangsu Province Laboratory of Electrical and Automation Engineering for Coal Mining, Xuzhou 221116, China
Abstract:
In order to make full use of the phase information of initial modulus traveling wave and overcome the error of traditional initial modulus traveling wave front identification method, a single-phase grounding fault location method is proposed based on the distortion characteristics and dispersion effect of the modulus traveling wave propagating on the transmission line, which locates single-phase grounding fault by using the phase relation between the same high-frequency components of initial zero-mode and aerial-mode voltage traveling waves at two-terminal measuring points. The proposed method does not require accurate synchronization at both terminals, nor does it depend on the arrival time of the modulus traveling waves and wave velocity information. The transmission line model is built on PSCAD and the simulation is carried out. The simulative results show the effectiveness and reliability of the proposed method.
Key words:  modulus traveling waves  distortion  phase relation  transmission line  electric fault location

用微信扫一扫

用微信扫一扫