引用本文:尹纯亚,李凤婷,陈伟伟,张增强.单极闭锁引起直流健全极换相失败分析[J].电力自动化设备,2019,39(11):
YIN Chunya,LI Fengting,CHEN Weiwei,ZHANG Zengqiang.Commutation failure risk analysis of sound pole caused by DC monopole blocking[J].Electric Power Automation Equipment,2019,39(11):
【打印本页】   【HTML】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 4026次   下载 1854  
单极闭锁引起直流健全极换相失败分析
尹纯亚1, 李凤婷1, 陈伟伟2, 张增强2
1.新疆大学 电气工程学院,新疆 乌鲁木齐 830047;2.国网新疆电力公司 经济技术研究院,新疆 乌鲁木齐 830011
摘要:
推导建立了换相失败的数学模型,得出送、受端换流母线电压比值是引起换相失败的主要原因,单极闭锁后健全极存在换相失败的风险。分析了单极闭锁引起暂态过电压的影响因素,并推导出直流闭锁后的暂态过电压定量计算解析表达式,提出一种单极闭锁后考虑两侧换流母线电压的换相失败判据,并得出送端、受端短路容量与换相失败的关系。最后基于DIgSILENT仿真平台搭建 ±800 kV天中直流输电系统仿真模型,仿真结果验证了暂态过电压计算方法的正确性,同时证明了单极闭锁后健全极存在换相失败的风险。
关键词:  高压直流输电  电力传输  换相失败  单极闭锁  暂态过电压  关断角
DOI:10.16081/j.epae.201910021
分类号:TM721.1;TM46
基金项目:国网新疆电力公司科技项目(SGXJJY00GHJS180?0065);新疆维吾尔自治区科技支疆项目(2017E0277)
Commutation failure risk analysis of sound pole caused by DC monopole blocking
YIN Chunya1, LI Fengting1, CHEN Weiwei2, ZHANG Zengqiang2
1.College of Electrical Engineering, Xinjiang University, Urumqi 830047, China;2.Economic Research Institute, State Grid Xinjiang Electric Power Corporation, Urumqi 830011, China
Abstract:
Based on the establishment of a mathematical CF(Commutation Failure) model, it is indicated that, the ratio of commutation bus voltage between send-terminal and receive-terminal is the main factor for CFs, and risk of sound pole CFs exists when a MPB(Mono-Pole Blocking) occurs. Influences leading to overvoltage when MPB occurs are analyzed, an expression for quantitative calculation of transient overvol-tage after MPB is deduced, and a criterion of CFs after MPB considering bus overvoltage at send-and receive-terminals is proposed, and the relationship between send/receive terminal short-circuit capacity and CFs is obtained. Based on a simulation model of ±800 kV HVDC(High Voltage Direct Current) system established on DIgSILENT, the validity of transient overvoltage calculation and risk of sound pole CFs existence are verified through simulations.
Key words:  HVDC power transmission  electric power transmission  commutation failure  DC monopole bloc-king  transient overvoltage  extinction angle