引用本文:贾科,杨哲,朱正轩,郑黎明,毕天姝.基于电流幅值比的逆变型新能源场站送出线路T接纵联保护[J].电力自动化设备,2019,39(12):
JIA Ke,YANG Zhe,ZHU Zhengxuan,ZHENG Liming,BI Tianshu.Pilot protection based on current amplitude ratio for teed line in inverter-interfaced renewable energy power plants[J].Electric Power Automation Equipment,2019,39(12):
【打印本页】   【HTML】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 12701次   下载 1580  
基于电流幅值比的逆变型新能源场站送出线路T接纵联保护
贾科, 杨哲, 朱正轩, 郑黎明, 毕天姝
华北电力大学 新能源电力系统国家重点实验室,北京 102206
摘要:
逆变型新能源的内阻抗不稳定、相角受控,因此比率制动式差动保护面临巨大挑战。为解决该问题,提出了基于两侧电流幅值比的纵联保护方法,同时分析了该方法在场站T接情况下的适应性并提出了改进判据。所提方法只需传递标量信号,降低了对通信系统和同步能力的要求,且在重合于永久性故障以及场站失电情况下均能正确动作,原理简单可靠,具备工程应用价值。仿真结果表明所提方法能够正确区分区内外故障,录波数据进一步证实了该方法的有效性。
关键词:  逆变型电源  继电保护  纵联保护  幅值比  送出线路
DOI:10.16081/j.epae.201912003
分类号:TM77
基金项目:国家重点研发计划资助项目(2016YFB0900203);国家自然科学基金资助项目(51777071,51407067);中央高校基本科研业务费专项资金资助项目(2016ZZD01)
Pilot protection based on current amplitude ratio for teed line in inverter-interfaced renewable energy power plants
JIA Ke, YANG Zhe, ZHU Zhengxuan, ZHENG Liming, BI Tianshu
State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University, Beijing 102206, China
Abstract:
The internal impedance of inverter-interfaced renewable energy generator is unstable and its phase angle is affected by control system, so the ratio braking style differential protection faces great challenges. To solve this problem, a pilot protection method based on current amplitude ratio of both sides is proposed. Meanwhile the adaptability of the proposed method in condition of teed line is analyzed and the improved criterion is put forward. The proposed method only needs to transmit the scalar signals, which reduces the requirements on the communication system and synchronizing ability. It can correctly operate in the case of reclosing on permanent faults and power failure. In addition, its principle is simple and reliable, and it has engineering application value. The simulative results show that the proposed method can correctly distinguish internal and external faults and field-testing data also confirm the effectiveness of the method.
Key words:  inverter-interfaced power generator  relay protection  pilot protection  amplitude ratio  transmission line