引用本文:张琦雪,马志恒,肖鹏,都成刚,王凯,杨扬,周荣斌,王强,王光.大型汽轮发电机组的扭振快速保护[J].电力自动化设备,2020,40(11):
ZHANG Qixue,MA Zhiheng,XIAO Peng,DU Chenggang,WANG Kai,YANG Yang,ZHOU Rongbin,WANG Qiang,WANG Guang.Fast torsional vibration protection for large steam turbine generator[J].Electric Power Automation Equipment,2020,40(11):
【打印本页】   【HTML】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 4614次   下载 1675  
大型汽轮发电机组的扭振快速保护
张琦雪, 马志恒, 肖鹏, 都成刚, 王凯, 杨扬, 周荣斌, 王强, 王光
南京南瑞继保电气有限公司,江苏 南京 211102
摘要:
串补电容可能引发次同步暂态扭矩放大,极端情况下在0.5 s内导致汽轮发电机组大轴损伤,常规扭应力保护来不及保护。提出一种快速保护方法,该方法将电流或有功功率的工频变化量越限作为启动判据,波动转速幅值越限作为动作判据。针对XM地区M电厂的机组,选取12个算例进行时域仿真分析,结果表明,波动转速幅值与扭振幅值有较好的一致性,近似成正比;在仿真的转速中叠加现场实测的转速噪声信号,对保护算法及保护逻辑进行验证,结果表明扭振较轻时保护不动作,扭振较重时保护快速动作,最恶劣工况下暂态扭矩放大导致的疲劳值可降低至15 %以下。需注意机组脱网之后仍存在扭振的影响,保护定值应有足够裕度。
关键词:  汽轮发电机  次同步谐振  次同步振荡  扭振保护  暂态扭矩放大  电容串补
DOI:10.16081/j.epae.202010014
分类号:TM77
基金项目:
Fast torsional vibration protection for large steam turbine generator
ZHANG Qixue, MA Zhiheng, XIAO Peng, DU Chenggang, WANG Kai, YANG Yang, ZHOU Rongbin, WANG Qiang, WANG Guang
NR Electric Co.,Ltd.,Nanjing 211102, China
Abstract:
The transient torque amplification which may be resulted from series compensated capacitor could lead to fatigue cracks in the shaft of a large steam turbine generator within 0.5 seconds, the conventional torsional stress relay cannot work in time to protect in this extreme case. A fast protection method is proposed, which takes the over-component of power frequency variation of current or active power as the pick-up criterion, and the over-amplitude of fluctuation speed amplitude as the operation criterion. For the turbine-generator units of the Power Plant M in XM grid of China, twelve cases are selected for time domain simulation study. The simulative results show that the speed deviation amplitudes are obviously consistent with the torsional torque amplitudes and they are approximately proportional. Finally, the speed signals of the simulation cases are superimposed with on-sited measured speed noises, and then the protection algorithm and logic are verified. The study shows the fast protection doesn’t operate when torsional vibration is slight, but trips fast when torsional vibration is severe, so that the fatigue value resulted from shaft torque amplification in the worst case will be decreased to less than 15 %. It should be noted that the effect of torsional vibration still exists after the generator is disconnected from the grid, and the protection setting threshold should have sufficient margin.
Key words:  steam turbine generator  subsynchronous resonance  subsynchronous oscillation  torsional vibration protection  transient shaft torque amplification  series compensated capacitor