摘要: |
针对启动1号给水泵时,1号发电机-变压器组差动保护有时会误动的情况,经过分析和计算 ,确认1号高压厂用变压器高压侧电流互感器C相二次出线IC441与ICN441接反,是造成差动保护误动的直接原因,经验证无误无,恢复了IC441与ICN441的正确接线,消除了主设备的主保护长期遗留下的事故隐患。 |
关键词: 给水泵 机组 误跳闸 故障分析 火力发电厂 |
DOI: |
分类号:TM621.7 |
基金项目: |
|
Analysis of unit protection misoperation when starting feed water pump |
LAI Wei-feng
|
Abstract: |
When start up No.1feed water pump ,the differential relay protection of No.1generator-trans-former set may happen misoperation.By analysis and calculation,it is confirmed that the secondary out puts I C441 and I CN441 on phase C of the current transformer at high voltage side of No.1high voltage transformer are reversedly connected.After in spection and verification,the mistake is corrected. |
Key words: differential relay protection,fault analy sis,prevention strategy, |