引用本文: | 黄健光,白忠林,戴雯霞.铜接地体技术在GIS变电站工程中的探索与实践[J].电力自动化设备,2004,(10):69-73 |
| .Research and practice of copper-made grounding device technique in GIS substation project[J].Electric Power Automation Equipment,2004,(10):69-73 |
|
|
摘要: |
铜接地体与常规热镀锌钢接地体相比,其导电性能好8倍,耐腐蚀性能强3倍,并且施工方便,更适用于六氟化硫气体绝缘全封闭组合电器GIS(SF6 Gas-Insulated Switchgear)变电站接地系统。结合广东省江门市220kV新会变电站和广东省台山发电厂220kV铜鼓升压站等GIS配电装置变电站工程实例,介绍了铜接地体截面面积计算、材料规格选择和连接方法;分析了铜接地体不同连接头的可靠性及其在施工中应注意的事项。 |
关键词: SF6气体绝缘全封闭组合电器 GIS 铜接地体 触摸电压 接地线连接头 |
DOI: |
分类号:TM241 TM63 |
基金项目: |
|
Research and practice of copper-made grounding device technique in GIS substation project |
HUANG Jian-guang 1 BAI Zhong-lin 2 DAI Wen-xia 3
|
Abstract: |
Compared with traditional zinced steel grounding device ,the copper-made grounding device is eight times better in conductivity ,three times stronger in erosion tolerance ,and con-venient in construction ,which makes it fit for GIS ( SF6Gas-Insulated Swichgear ) substation groun-ding system.With the GIS substation projects for220kV substation and220kV power plant voltage-raising station as examples ,techniques for copper-made grounding device are introduced ,including cross sectional area calculation ,material selection and connection methods.The reliability of copper-made grounding device with different connection types is analyzed ,and cautions in construction are advised. |
Key words: GIS,copper-made grounding device,touch voltage,grounding electrical connection |