摘要: |
利用ATP电磁暂态仿真计算程序,对影响过电压的各种因素进行了理论分析,并根据变电站的实例和数据参数建立了仿真计算模型,针对影响配电网过电压的几个因素分别进行了仿真。仿真数据表明单相接地过电压受燃弧时刻、电弧电阻、故障距离和系统对地电容的影响各不相同,其中燃弧时刻对过电压的影响最明显,电弧电阻的影响次之,故障距离和系统对地电容对过电压的影响较小。 |
关键词: 配电网 单相接地 仿真 故障相电压 过电压 |
DOI: |
分类号: |
基金项目: |
|
Simulative calculation of 10 kV network single-phase grounding overvoltage |
XU Fei
|
Guangxi Power Test & Research Institute,Nanning 530023,China
|
Abstract: |
The various factors causing overvoltage are theoretically researched with ATP(Alternative Transient Program) and the simulation model is established according to the data of a real substation. Several factors causing distribution network overvoltage are simulated:arc occurrence instant,arc resistance,fault distance,system-to-ground capacitance. Results show that their influences on single-phase grounding overvoltage are different:the arc occurrence instant has the greatest influence and the arc resistance has less influence, while the fault distance and system-to-ground capacitance have the least influence. |
Key words: distribution network single-phase grounding simulation faulty phase voltage overvoltage |