引用本文: | 李正红,文小平.一起220 kV断路器单相拒合故障分析及防范措施[J].电力自动化设备,2011,31(5): |
| LI Zhenghong,WEN Xiaoping.Analysis of 220 kV circuit breaker single-phase closing failure and its countermeasures[J].Electric Power Automation Equipment,2011,31(5): |
|
摘要: |
针对某次220 kV线路保护装置定期检验过程中出现断路器c相拒合故障进行了调查,发现是由于断路器机构合闸线圈接触不良造成的。通过设计合闸保护回路,增加了合闸回路延时断开功能,并验证了此方法可以有效解决当断路器出现拒合故障时烧毁合闸线圈和操作箱合闸插件的问题。从现场作业的角度阐述了采用快速切断操作电源、测量分析合闸回路电阻、做好定期检验工作等措施来防止此类故障的发生。 |
关键词: 断路器 二次回路 继电保护 故障分析 |
DOI: |
分类号: |
基金项目: |
|
Analysis of 220 kV circuit breaker single-phase closing failure and its countermeasures |
LI Zhenghong1, WEN Xiaoping2
|
1.Shenzhen Power Supply Bureau,Shenzhen 518020,China;2.Sichuan University,Chengdu 610064,China
|
Abstract: |
Phase-c closing failure of a circuit breaker is found during the regular inspection for a 220 kV line protection,which is caused by the poor connection of circuit breaker’s closing winding. A protective circuit is designed to add delayed-trip function to the closing circuit,which effectively prevents the burning of closing winding and intermediate relay when closing failure of circuit breaker occurs. The countermeasures are proposed:quickly switch off the operating power;measure the resistance of closing circuit;inspect regularly. |
Key words: circuit breaker secondary circuit relay protection failure analysis |