引用本文:李 扬,苏慧玲.N - k故障下影响电力系统脆弱性的关键线路研究[J].电力自动化设备,2015,35(3):
LI Yang,SU Huiling.Critical line affecting power system vulnerability under N-k contingency condition[J].Electric Power Automation Equipment,2015,35(3):
【打印本页】   【HTML】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 4704次   下载 0  
N - k故障下影响电力系统脆弱性的关键线路研究
李 扬1, 苏慧玲1,2
1.东南大学 电气工程学院,江苏 南京 210096;2.国网江苏省电力公司电力科学研究院,江苏 南京 211103
摘要:
为研究N-k故障下导致电力系统脆弱性恶化的关键线路,提出一种构建关键线路模型的方法。基于脆弱性概念和复杂网络脆弱性理论,以电力系统最小失负荷率来表示电力网络的实际传输效率,建立电力系统脆弱性模型;基于协同破坏效应理论,结合N-k故障下故障集的脆弱性,建立故障情况下影响电力系统脆弱性的关键线路模型;考虑系统中两两相邻线路可能具有相似的特点,提出基于分区划分法的分析流程。IEEE 39节点系统算例仿真结果表明,所提模型和方法能够有效筛选故障集的数目,并得出高脆弱线路具有低协同破坏效应、高关键线路具有高协同破坏效应和低脆弱性的结论。
关键词:  协同效应  电力系统  脆弱性  关键线路  最小失负荷率  分区划分法
DOI:
分类号:
基金项目:基金项目:国家电网公司千人计划项目
Critical line affecting power system vulnerability under N-k contingency condition
LI Yang1, SU Huiling1,2
1.School of Electrical Engineering,Southeast University,Nanjing 210096,China;2.Jiangsu Electric Power Company Research Institute,Nanjing 211103,China
Abstract:
In order to study the critical lines leading to power system vulnerability deterioration under N- k contingency condition,a method of building the critical line model is proposed. Based on the concept of vulnerability and the vulnerability theory of complex network,a model of power system vulnerability is set up,which adopts the minimum load-shedding rate to express the practical transmission efficiency of power grid. Based on the theory of synergistic damage effect and the vulnerability of failure set under N- k contingency condition,a model of critical line affecting the vulnerability of power system under fault condition is built. With the consideration that the adjacent lines may have similar characteristic,an analysis flowchart based on the partition method is proposed. Simulative results of IEEE 39-bus system show the proposed model and method can effectively screen the failure sets. The obtained conclusion is:the highly vulnerable line has low synergistic damage effect while the highly critical line has high synergistic damage effect with low vulnerability.
Key words:  synergistic effect  electric power systems  vulnerability  critical line  minimum load-shedding rate  partition method