引用本文:周 浩,李济沅,王东举,邱玉婷,李 莎,韩雨川.±800 kV特高压直流输电线路单极接地故障过电压产生机理及影响因素[J].电力自动化设备,2016,36(4):
ZHOU Hao,LI Jiyuan,WANG Dongju,QIU Yuting,LI Sha,HAN Yuchuan.Overvoltage generation mechanism during single-pole grounding fault of ± 800 kV UHVDC transmission lines and its influencing factors[J].Electric Power Automation Equipment,2016,36(4):
【打印本页】   【HTML】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 4905次   下载 2377  
±800 kV特高压直流输电线路单极接地故障过电压产生机理及影响因素
周 浩, 李济沅, 王东举, 邱玉婷, 李 莎, 韩雨川
浙江大学 电气工程学院,浙江 杭州 310027
摘要:
将特高压直流输电线路单极接地故障过电压分成第一次跃升和第二次跃升2个过程,并基于极线间的电磁耦合作用和波过程阐述了2次电压跃升的产生机理;分析了直流滤波器主电容、直流滤波器型式、直流控制系统、杆塔接地电阻、线路中点杆塔是否装设避雷器、输电线路参数和输送功率等多种因素对该过电压的影响。仿真结果表明,直流滤波器主电容参数是限制单极接地故障过电压的关键因素,其他因素对该过电压影响不大,为控制过电压幅值不超过额定电压的1.7倍,建议 ± 800 kV特高压线路的直流滤波器主电容参数取值范围为1~2 μF。
关键词:  特高压输电  直流输电  单极接地故障  过电压  机理分析  故障分析  影响因素  波过程
DOI:
分类号:
基金项目:国家重点基础研究发展计划(973计划)资助项目(2011CB209405)
Overvoltage generation mechanism during single-pole grounding fault of ± 800 kV UHVDC transmission lines and its influencing factors
ZHOU Hao, LI Jiyuan, WANG Dongju, QIU Yuting, LI Sha, HAN Yuchuan
College of Electrical Engineering,Zhejiang University,Hangzhou 310027,China
Abstract:
The overvoltage process of single-pole grounding fault of UHVDC transmission line is divided into two parts:the first voltage jump and the second voltage jump. The generation mechanism of two voltage jumps is studied based on the electromagnetic coupling between two poles and the wave process. The influences of different factors on the overvoltage are analyzed,such as main DC filter capacitor,DC filter type,DC control system,grounding resistance of line tower,arrester installed on tower at line midpoint,transmission line parameters,transferring power,etc. Simulative results show that,the main capacitor of DC filter is a critical factor to limit the overvoltage while the others have little effect on the overvoltage. Recommended capacitance of the main capacitor of DC filter for ± 800 kV UHVDC lines is from 1 μF to 2 μF for limiting the overvoltage within 1.7 times of rated voltage.
Key words:  UHV power transmission  DC power transmission  single-pole grounding fault  overvoltage  mechanism analysis  failure analysis  influencing factors  wave process