引用本文:李振柱,谢志成,熊卫红,张宏志,李正天,林湘宁,涂长庚.考虑绝缘剩余寿命的变压器健康状态评估方法[J].电力自动化设备,2016,36(8):
LI Zhenzhu,XIE Zhicheng,XIONG Weihong,ZHANG Hongzhi,LI Zhengtian,LIN Xiangning,TU Changgeng.Transformer health condition assessment considering insulation remaining life[J].Electric Power Automation Equipment,2016,36(8):
【打印本页】   【HTML】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 4067次   下载 1724  
考虑绝缘剩余寿命的变压器健康状态评估方法
李振柱1, 谢志成2, 熊卫红1, 张宏志2, 李正天2, 林湘宁2, 涂长庚1
1.国家电网公司华中分部,湖北 武汉 430077;2.华中科技大学 强电磁工程与新技术国家重点实验室,湖北 武汉 430074
摘要:
在现有的健康指数理论和绝缘寿命计算方法的基础上进行延伸和拓展,建立变压器运行状态评估结果与其剩余寿命的映射关系,提出了一种考虑绝缘剩余寿命的油浸式变压器健康状态评估方法。利用变压器负荷记录和环境温度数据计算设备热点温度,继而计算设备的绝缘剩余寿命;再根据分级评估的思想对变压器运行状态进行分级评估,考虑不同因素的影响,形成不同层级的健康指数修正因子,最终得到反映变压器的综合运行状态的设备剩余寿命及健康指数评分。通过实际变电站算例分析证明了该方法的有效性和优越性。该方法并不局限于油浸式变压器,对于其他油绝缘设备(如电抗器)同样适用。
关键词:  变压器  绝缘剩余寿命  健康指数理论  分级评估  修正因子
DOI:
分类号:
基金项目:中央高校基本科研业务费资助项目(HUST:2014QNR-C042);国家电网公司科技项目
Transformer health condition assessment considering insulation remaining life
LI Zhenzhu1, XIE Zhicheng2, XIONG Weihong1, ZHANG Hongzhi2, LI Zhengtian2, LIN Xiangning2, TU Changgeng1
1.Central China Electric Power Company,Wuhan 430077,China;2.State Key Laboratory of Advanced Electromagnetic Engineering and Technology,Huazhong University of Science and Technology,Wuhan 430074,China
Abstract:
A method of health condition assessment considering its insulation remaining life is proposed for oil-immersed power transformers,which extends the existing health index theory and the insulation life calculation method to establish the mapping relationship between the result of transformer operating condition assessment and its remaining life. The hot-spot temperature of transformer is calculated according to its load records and environmental temperature data,based on which,its insulation remaining life is calculated. The concept of classification evaluation is applied to evaluate the operating conditions of transformer in different classes,which considers different influencing factors to form the health index correction factors for different classes and calculates the remaining life and health index score to reflect the comprehensive operating condition of transformer. Sample analysis for an actual substation proves the validity and superiority of the proposed method. The method can also be applied to other oil-charged equipments(such as reactor).
Key words:  electric transformers  insulation remaining life  health index theory  classification evaluation  correction factor

用微信扫一扫