引用本文:马朋,刘青,邹家平,刘诚.UPFC有功控制引起的交互影响研究[J].电力自动化设备,2017,37(1):
MA Peng,LIU Qing,ZOU Jiaping,LIU Cheng.Research on interaction during active power-flow control of UPFC[J].Electric Power Automation Equipment,2017,37(1):
【打印本页】   【HTML】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 4059次   下载 1367  
UPFC有功控制引起的交互影响研究
马朋1, 刘青1, 邹家平2, 刘诚3
1.华北电力大学 新能源电力系统国家重点实验室,河北 保定 071003;2.广东国华粤电台山发电有限公司,广东 台山 529228;3.中国神华能源股份有限公司国华惠州热电分公司,广东 惠州 516082
摘要:
统一潮流控制器(UPFC)的多个控制器之间存在交互影响,这种交互作用会影响控制器的工作性能。分析了UPFC有功参考值的变化对电压控制器所控电压的影响,阐述了利用数学公式反映其影响的方法的局限性。利用PSCAD/EMTDC时域仿真,得出了电压动态数据,并用来拟合Logistic模型,得到有功补偿度变化量对节点电压变动值影响的数学表达式。该数学表达式能够针对不同有功补偿度变化量进行交互影响程度的预测,有利于分析UPFC有功潮流控制给并联侧电压控制器运行带来的影响。
关键词:  统一潮流控制器  交互影响  潮流控制  电压控制器  电压变动值  Logistic模型
DOI:10.16081/j.issn.1006-6047.2017.01.028
分类号:
基金项目:
Research on interaction during active power-flow control of UPFC
MA Peng1, LIU Qing1, ZOU Jiaping2, LIU Cheng3
1.State Key Laboratory of Alternate Electrical Power System with Renewable Energy Source, North China Electric Power University, Baoding 071003, China;2.Guohua Yuedian Taishan Power GenerationCompany Ltd.,Taishan 529228, China;3.Guohua Huizhou Cogeneration Branch Company of Shenhua Energy Company Ltd.,Huizhou 516082, China
Abstract:
There are interactions among the sub-controllers of UPFC(Unified Power Flow Controller),which may affect its control performance. The effect of the active-power reference change of UPFC on the controlled voltage of its voltage controller is analyzed and the limitation of applying mathematical formula to reflect this effect is expounded. The time-domain simulation with PSCAD/EMTDC is carried out to obtain the dynamic data of voltage, which are used to fit a Logistic model for deducing a mathematical expression to describe the effect of active-power compensation degree on the nodal voltage variation. The deduced expression is then applied to predict the interaction degree according to the active-power compensation degree, which is then used to analyze the effect of UPFC active power-flow control on the operation of its voltage controller at parallel side.
Key words:  unified power flow controller  interactions  power-flow control  voltage controller  voltage fluctuation value  Logistic model

用微信扫一扫

用微信扫一扫