引用本文: | 肖峻,蒋迅,郭伟,李蕴,黄仁乐,陈平.分区柔性互联城市电网的最大供电能力分析[J].电力自动化设备,2017,37(8): |
| XIAO Jun,JIANG Xun,GUO Wei,LI Yun,HUANG Renle,CHEN Ping.Total power-supply capability of urban power grid with flexibly-interconnected partitions[J].Electric Power Automation Equipment,2017,37(8): |
|
摘要: |
对比现有电网分区运行模式与新型柔性互联运行模式,并阐述柔性直流分区互联装置的基本工作模式;介绍分区互联装置的基本结构,并研究装置在分区间有功支援与动态无功支撑过程中的工作原理;考虑电网N-1静态安全性与暂态电压稳定性,提出分区柔性互联城市电网最大供电能力的定义与模型,并给出一种简化的逼近求解算法。某电网示范工程实际算例验证了所提方法的正确性;与传统分区运行相比,柔性互联后最大供电能力得到提升。 |
关键词: 分区 柔性互联 城市电网 最大供电能力 分区互联装置 |
DOI:10.16081/j.issn.1006-6047.2017.08.009 |
分类号:TM761 |
基金项目:国家高技术研究发展计划(863计划)资助项目(2015A-A050102);国家自然科学基金资助项目(51277129) |
|
Total power-supply capability of urban power grid with flexibly-interconnected partitions |
XIAO Jun1, JIANG Xun1, GUO Wei2, LI Yun3, HUANG Renle3, CHEN Ping3
|
1.Key Laboratory of Smart Grid of Ministry of Education, Tianjin University, Tianjin 300072, China;2.State Grid Tianjin Electric Power Company, Tianjin 300000, China;3.State Grid Beijing Electric Power Company, Beijing 100031, China
|
Abstract: |
The novel flexibly-interconnected operating modes of power grid is compared with the present partitioned operating mode and the basic working modes of flexible DC inter-partition connecting device are analyzed. The basic structure of inter-partition connecting device is introduced and its working principles during the active-power support and the dynamic reactive-power support among partitions are investigated. With the consideration of N-1 static security and transient voltage stability of power grid, the definition and model of total power-supply capability of urban power grid with flexibly-interconnected partitions are proposed and a simplified approximation method is given to solve it. Case study for a pilot project verifies the correctness of the proposed method. Compared with the traditional partitioned operation, the total power-supply capability of flexibly-interconnected partitions is enhanced. |
Key words: partition flexibly-interconnected urban power network total power-supply capability inter-partition connecting device |