引用本文: | 李兴建,笃峻,于哲,赵玉灿,黄辉,许宗光.合并单元时钟同步测试装置的研制及应用[J].电力自动化设备,2017,37(12): |
| LI Xingjian,DU Jun,YU Zhe,ZHAO Yucan,HUANG Hui,XU Zongguang.Development and application of clock synchronization tester for MU[J].Electric Power Automation Equipment,2017,37(12): |
|
摘要: |
针对合并单元缺乏时钟同步异常状况测试的现状,设计了一种测试装置,该装置既能够自产生各种IRIG-B异常信号,又能够监视外接IRIG-B信号。利用该装置组成了自动化测试系统,通过自动化闭环测试方法,校验合并单元在时钟同步信号异常的情况下各种性能表现,补充了合并单元测试的测试手段,有助于提高合并单元的可靠性。 |
关键词: 时钟同步 自动测试 合并单元 IRIG-B |
DOI:10.16081/j.issn.1006-6047.2017.12.031 |
分类号:TM73 |
基金项目: |
|
Development and application of clock synchronization tester for MU |
LI Xingjian, DU Jun, YU Zhe, ZHAO Yucan, HUANG Hui, XU Zongguang
|
Nanjing NR Electric Co.,Ltd.,Nanjing 211102, China
|
Abstract: |
Aiming at the lack of abnormal clock synchronization test for MU(Merging Unit),a clock synchronization tester is designed, which not only can generate abnormal signal of IRIG-B, but also monitor the IRIG-B signal from external GPS device. A kind of automatic test system is constructed with the designed tester to investigate the performance of MU functions in the clock synchronization abnormal by automatic closed-loop test method, supplement the testing measurement of MU and help to improve the reliability of MU. |
Key words: clock synchronization automatic test merging unit IRIG-B |