引用本文:赵万宗,韦化,韦昌福,鲍海波.考虑市场力风险约束的最优AGC控制模型[J].电力自动化设备,2018,(5):
ZHAO Wanzong,WEI Hua,WEI Changfu,BAO Haibo.Optimal AGC model with risk constraints of market power[J].Electric Power Automation Equipment,2018,(5):
【打印本页】   【HTML】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 5320次   下载 1850  
考虑市场力风险约束的最优AGC控制模型
赵万宗1, 韦化1, 韦昌福2, 鲍海波1
1.广西大学 广西电力系统最优化与节能技术重点实验室,广西 南宁 530004;2.广西电网电力调度控制中心,广西 南宁 530023
摘要:
针对传统自动发电控制(AGC)优化模型中难以考虑市场力风险的问题,引入度量市场风险的价值模型,提出了以风险价值为限值的辅助服务成本约束混合整数非线性规划的AGC优化模型。为处理模型的非线性,引入两态辅助变量,将三态的机组状态变量进行等效转化,实现了模型的线性化,有效地降低了模型求解难度。以广西电网运行数据为例,对比不同风险置信水平下AGC控制性能,结果表明:置信水平越高,调节成本越大,控制效果越好,但无论置信水平高低,所提模型均能确保控制性能标准(CPS)合格,验证了模型的有效性,为电力市场环境下的AGC控制提供了有益参考。
关键词:  自动发电控制  市场力  风险价值  辅助服务  控制性能标准
DOI:10.16081/j.issn.1006-6047.2018.05.011
分类号:TM71
基金项目:国家重点基础研究发展计划(973计划)资助项目(2013CB228205);国家自然科学基金资助项目(51667003)
Optimal AGC model with risk constraints of market power
ZHAO Wanzong1, WEI Hua1, WEI Changfu2, BAO Haibo1
1.Guangxi Key Laboratory of Power System Optimization and Energy Technology, Guangxi University, Nanning 530004, China;2.Guangxi Power Grid Dispatching Control Center, Nanning 530023, China
Abstract:
Aiming at the problem that the market power risk is difficult to be considered in the traditional AGC(Automatic Generation Control) optimization model, the VaR(Value at Risk) for measuring market risk is introduced, and the AGC optimization model of mixed integer nonlinear programming under the constraint of ancillary service cost with VaR as the limit value is constructed. For dealing with the nonlinearity of the model, the two-state auxiliary variables are introduced to equivalently transform the three-state variables of the unit, which realizes the linearization of the model and thus effectively reduces the difficulty of solving the model. Taking the operation data of Guangxi Power Grid as an example, the performances of AGC under different risk confidence levels are compared. The results show that the higher the confidence level is, the greater the regulation cost will be, but with better control effect. However, whether the confidence level is high or not, the proposed model can ensure the CPS(Control Performance Standard) qualification, verifying the validity of the model. It can provide a useful reference for the AGC in the power market environment.
Key words:  automatic generation control  market power  value at risk  auxiliary service  control performance standard

用微信扫一扫

用微信扫一扫