引用本文:郑含博,张镱议,刘捷丰,房加珂.一种油浸式电力变压器纸绝缘老化评估新特征量[J].电力自动化设备,2018,(10):
ZHENG Hanbo,ZHANG Yiyi,LIU Jiefeng,FANG Jiake.Novel characteristic products of paper insulation aging assessment for oil-immersed power transformer[J].Electric Power Automation Equipment,2018,(10):
【打印本页】   【HTML】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 4109次   下载 1764  
一种油浸式电力变压器纸绝缘老化评估新特征量
郑含博1,2, 张镱议1, 刘捷丰1,3, 房加珂1
1.广西大学广西电力系统最优化与节能技术重点实验室,广西南宁530004;2.国网河南省电力公司电力科学研究院,河南郑州450052;3.国网河北省电力公司石家庄供电分公司,河北石家庄050000
摘要:
针对油中糠醛含量随变压器运行时间变化的分散性较大,难以准确评估油浸式变压器纸绝缘老化状态的不足,对甲醇、乙醇等低分子醇作为变压器纸绝缘老化评估新特征量进行了理论分析与实验研究。对绝缘纸的老化机理以及化学键断裂进行分析,从理论上探究甲醇、乙醇等低分子醇的产生原理及主要生成途径。采用气相色谱质谱联用法对现场2台老旧变压器绝缘油样品中的甲醇、乙醇及糠醛含量进行了测定。实验结果表明,2组样品中均未检测到糠醛,但却检测到数量可观的乙醇。进一步地,对现场2台刚投运变压器的检测结果对比分析,分析结果揭示了乙醇可以作为一种有效表征变压器绝缘纸老化的新特征量,且比糠醛特征量相比更为有效。
关键词:  油浸式变压器  纸绝缘  老化评估  乙醇  低分子醇
DOI:10.16081/j.issn.1006-6047.2018.10.023
分类号:TM41
基金项目:国家自然科学基金资助项目(51867003);广西自然科学基金资助项目(2015GXNSFBA139235);广西科技厅资助项目(AE020069);广西教育厅资助项目(T3020097903)
Novel characteristic products of paper insulation aging assessment for oil-immersed power transformer
ZHENG Hanbo1,2, ZHANG Yiyi1, LIU Jiefeng1,3, FANG Jiake1
1.Guangxi Key Laboratory of Power System Optimization and Energy Technology, Guangxi University, Nanning 530004, China;2.Electric Power Research Institute of State Grid Henan Electric Power Company, Zhengzhou 450052, China;3.Hebei Electric Power Dispatching and Control Center, Shijiazhuang 050000, China
Abstract:
The furfural content in oil may dispersedly change along with the operating time of transformer, which makes it difficult to evaluate the paper insulation aging status of oil-immersed transformers. To overcome this shortage, the methanol, ethanol and other low molecular alcohols are theoretically analyzed and experimentally verified as new characteristic products of paper insulation aging evaluation. The generation principles and ways of low molecular alcohols such as methanol and ethanol are theoretically explored by analyzing the aging mechanism of insulating paper and the order of chemical bond breaking. The content of furfural, methanol and ethanol in two groups of insulating oil samples obtained from two old transformers are measured by gas chromatography-mass spectrometry. The experimental results show that no furfural but a considerable amount of ethanol is detected in the two groups of samples. Moreover, the detecting results of the two transformers newly put into operation are compared, the results show that compared with furfural, ethanol can be used as a more effective characteristic product to present the aging of transformer insulation paper.
Key words:  oil-immersed transformers  paper insulation  aging assessment  ethanol  low molecular alcohols

用微信扫一扫

用微信扫一扫