引用本文:翁汉琍,饶丹青,李振兴,黄景光,贾永波,陈皓.应用两端电流采样值二维空间映射分布特征的线路纵联保护[J].电力自动化设备,2020,40(8):
WENG Hanli,RAO Danqing,LI Zhenxing,HUANG Jingguang,JIA Yongbo,CHEN Hao.Transmission line pilot protection applying two-dimensional space mapped distribution characteristics of current sampling values at both ends[J].Electric Power Automation Equipment,2020,40(8):
【打印本页】   【HTML】   【下载PDF全文】   查看/发表评论  【EndNote】   【RefMan】   【BibTex】
←前一篇|后一篇→ 过刊浏览    高级检索
本文已被:浏览 4116次   下载 1737  
应用两端电流采样值二维空间映射分布特征的线路纵联保护
翁汉琍, 饶丹青, 李振兴, 黄景光, 贾永波, 陈皓
三峡大学 梯级水电站运行与控制湖北省重点实验室,湖北 宜昌 443002
摘要:
针对传统纵联保护在区外故障伴随电流互感器饱和时发生误动作的问题,提出一种基于线路两端电流采样值映射于二维空间分布特征差异的线路纵联保护新方案。该方案以线路两端电流采样点(母线指向线路为正方向)为坐标点映射于二维空间,在线路正常运行和外部故障工况下,映射点位于二维平面坐标系的第二、四象限;而内部故障工况下,映射点位于平面坐标系的第一、三象限。仿真和动模试验结果表明,所提方案能快速有效识别输电线路中出现的各类故障,对伴随电流互感器饱和及异常数据的故障也能正确识别。
关键词:  继电保护  线路纵联保护  二维空间映射  采样值分布特征  异常采样数据干扰  电流互感器饱和
DOI:10.16081/j.epae.202006030
分类号:TM77
基金项目:国家自然科学基金资助项目(51607106);梯级水电站运行与控制湖北省重点实验室(三峡大学)开放基金资助项目(2018KJX05)
Transmission line pilot protection applying two-dimensional space mapped distribution characteristics of current sampling values at both ends
WENG Hanli, RAO Danqing, LI Zhenxing, HUANG Jingguang, JIA Yongbo, CHEN Hao
Hubei Provincial Key Laboratory for Operation and Control of Cascaded Hydropower Station, China Three Gorges University, Yichang 443002, China
Abstract:
In order to solve the mal-operation problem of the traditional protection in case of external faults accompanied by current transformer saturation, a novel scheme for transmission line pilot protection based on the difference of two-dimensional space mapped distribution characteristics of current sampling values at both ends of the line is proposed. The current sampling values at both ends of the transmission line, the positive direction of which is defined as from bus to line, are mapped to the two-dimensional space. Under the normal operation and external fault conditions, the mapping points are located in the second and fourth quadrants of the two-dimensional plane coordinate system, while under the internal fault conditions, the mapping points are located in the first and third quadrants. The results of simulation and dynamic analog tests indicate that the proposed scheme can rapidly and effectively identify various types of faults in transmission lines, including the faults accompanied with current transformer saturation and abnormal data.
Key words:  relay protection  transmission line pilot protection  two-dimensional space mapping  distribution characteristics of sampling values  abnormal sampling data interference  current transformer saturation

用微信扫一扫

用微信扫一扫