引用本文: | 孔永科,王增平,刘青,吴烽,彭谦.TCSC与FSC对线路保护影响的对比分析[J].电力自动化设备,2005,(4):36-39 |
| .Comparative analysis of influences of TCSC and FSC on protective relaying for transmission line[J].Electric Power Automation Equipment,2005,(4):36-39 |
|
|
摘要: |
在分析可控串联电容补偿器TCSC(Thyristor-Controlled Series Capacitor)的运行模式、故障后的动作行为和动态基频阻抗特点的基础上。对比常规串联电容补偿器FSC(Fixed Series Compensation)。分析了TCSC对距离保护、方向元件及纵联保护的影响,认为:与FSC的线路相比,在TCSC线路上保护的性能不会降低,在FSC线路上运行的保护,可以在TCSC线路上很好地运行。 |
关键词: 可控串联电容补偿器 常规串联电容补偿器 距离保护 方向元件 纵联保护 |
DOI: |
分类号:TM773 |
基金项目: |
|
Comparative analysis of influences of TCSC and FSC on protective relaying for transmission line |
KONG Yong-ke WANG Zeng-ping LIU Qing WU Feng PENG Qian
|
Abstract: |
s:Based on the analysis of running mode,action after fault,dynamic power frequency impedance of TCSC(Thyristor-Controlled Series Capacitor) and compared with FSC(Fixed Series Compensation),the influence of TCSC on distance protection,direction component and pilot protection are analyzed. Protective relaying for lines with FCS may run well on lines with TCSC,and its protective performance will not become worse. |
Key words: TCSC,FSC,distance protection,direction component,pilot protection |